Field settings table
Breadcrumb
Field code
Setting name
9.I
[4-06]
Emergency
9.I
[4-08]
Which power limitation mode is required on the system?
9.I
[4-09]
Which power limitation type is required?
9.I
[4-0A]
Backup heater configuration
9.I
[4-0B]
Automatic cooling/heating changeover hysteresis.
9.I
[4-0D]
Automatic cooling/heating changeover offset.
9.I
[4-0E]
--
9.I
[5-00]
Equilibrium: Deactivate backup heater (or external backup heat source in case of a
bivalent system) above the equilibrium temperature for space heating?
9.I
[5-01]
What is the equilibrium temperature for the building?
9.I
[5-02]
Space heating priority.
9.I
[5-03]
Space heating priority temperature.
9.I
[5-04]
Set point correction for domestic hot water temperature.
9.I
[5-05]
What is the requested limit for DI1?
9.I
[5-06]
What is the requested limit for DI2?
9.I
[5-07]
What is the requested limit for DI3?
9.I
[5-08]
What is the requested limit for DI4?
9.I
[5-09]
What is the requested limit for DI1?
9.I
[5-0A]
What is the requested limit for DI2?
9.I
[5-0B]
What is the requested limit for DI3?
9.I
[5-0C]
What is the requested limit for DI4?
9.I
[5-0D]
Backup heater voltage
9.I
[5-0E]
BUH DHW thermo ON delay
9.I
[6-00]
The temperature difference determining the heat pump ON temperature.
9.I
[6-01]
The temperature difference determining the heat pump OFF temperature.
9.I
[6-02]
--
9.I
[6-03]
What is the capacity of the backup heater step 1?
9.I
[6-04]
What is the capacity of the backup heater step 2?
9.I
[6-07]
--
9.I
[6-08]
What is the hysteresis to be used in reheat mode?
9.I
[6-09]
--
9.I
[6-0A]
What is the desired comfort storage temperature?
9.I
[6-0B]
What is the desired eco storage temperature?
9.I
[6-0C]
What is the desired reheat temperature?
9.I
[6-0D]
What is the desired DHW production type?
9.I
[6-0E]
What is the maximum DHW temperature setpoint?
9.I
[7-00]
--
9.I
[7-01]
--
9.I
[7-02]
How many leaving water temperature zones are there?
9.I
[7-03]
--
9.I
[7-04]
--
9.I
[7-05]
Boiler efficiency
9.I
[7-06]
Compressor forced off
9.I
[7-07]
BBR16 activation
9.I
[7-08]
DHW stratification
9.I
[7-09]
Settable lower limit for the PWM of the pump
9.I
[7-0A]
Additional zone fixed pump PWM, in case a bizone kit is installed.
9.I
[7-0B]
Main zone fixed pump PWM, in case a bizone kit is installed.
(*1) *6V_(*2) *9W_
(*3) *18*_(*4) *23*_
(*5) + EKHVCONV4
Range, step
Default value
R/W
0: Manual
1: Automatic(normal SH/DHW ON)
2: Auto red SH/DHW ON
3: Auto red SH/DHW OFF
4: SH ON/DHW OFF
R/W
0: No limitation
1: Continuous
2: Digital inputs
R/W
0: Current
1: Power
R/W
0: 1
1: 1/1+2
2: 1/2
3: 1/2 + 1/1+2 in emergency
R/W
1~10°C, step: 0,5°C
1°C
R/W
1~10°C, step: 0,5°C
3°C
6
R/W
0: No
1: Yes
R/W
-15~35°C, step: 1°C
0°C
R/W
0: Disabled
1: Enabled
R/W
-15~35°C, step: 1°C
0°C
R/W
0~20°C, step: 1°C
10°C
R/W
0~50 A, step: 1 A
50 A
R/W
0~50 A, step: 1 A
50 A
R/W
0~50 A, step: 1 A
50 A
R/W
0~50 A, step: 1 A
50 A
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W
0~20 kW, step: 0,5 kW
20 kW
R/W (*1)
0: 230V, 1~ (*1)
R/O (*2)
1: 230V, 3~ (*1)
2: 400V, 3~ (*2)
R/W
0: Disable
1: Enable (variable delay HP dependent)
2: Enable (fixed delay HP dependent)
R/W
2~40°C, step: 1°C
8°C
R/W
0~10°C, step: 1°C
0°C
R/W
0
R/W
0~10kW, step: 0,2kW
2kW (*1)
3kW (*2)
R/W
0~10kW, step: 0,2kW
4kW (*1)
6kW (*2)
0
R/W
2~20°C, step: 1°C
10°C
0
R/W
30~[6-0E]°C, step: 1°C
55°C
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
R/W
0: Reheat only
1: Reheat + sched.
2: Scheduled only
R/W
40~65°C, step: 1°C
60°C
0
2
R/W
0: Single zone
1: Dual zone
2.5
0
R/W
0: Very high
1: High
2: Medium
3: Low
4: Very low
R/W
0: Disabled
1: Enabled
R/W
0: Disabled
1: Enabled
R/W
0: Disabled
1: Enabled
R/W
20
R/W
20~95%, step 5%
95%
R/W
20~95%, step 5%
95%
9/12
Installer setting at variance with
default value
Date
Value
4P655202-1 - 2021.09