Daikin EBVZ-D9W Installer's Reference Manual page 183

Table of Contents

Advertisement

ERLA11~16D + EBVZ16S18+23D
Daikin Altherma 3 R F
4P643604-1B – 2022.05
NOTICE
If there are 2 zones and the emitter types are wrongly configured, water of high
temperature can be sent towards a low temperature emitter (underfloor heating). To
avoid this:
Install an aquastat/thermostatic valve to avoid too high temperatures towards a
low temperature emitter.
Make sure you set the emitter types for the main zone [2.7] and for the
additional zone [3.7] correctly in accordance with the connected emitter.
Pump operation mode
When the space heating/cooling operation is OFF, the pump is always OFF. When
space heating/cooling operation is ON, you have the choice between these
operation modes:
#
Code
[4.5]
[F–0D]
Description
Pump operation mode:
0 Continuous: Continuous pump operation,
regardless of thermo ON or OFF condition.
Remark: Continuous pump operation requires
more energy than sample or request pump
operation.
a
b
c
b
c
d
a Space heating/cooling control
b Off
c On
d Pump operation
11
Configuration
|
Installer reference guide
183