Smart Grid Capacity Limitation Due To Buffering; Setting Up An External Temperature Sensor - Daikin EBVZ-D9W Installer's Reference Manual

Table of Contents

Advertisement

6
|
Application guidelines

6.5.5 Smart Grid capacity limitation due to buffering

6.6 Setting up an external temperature sensor

Installer reference guide
48
Set the power consumption control settings in [9.9] via the user interface (see
"Power consumption
-
Activate BBR16
-
Set the desired power limitation level
Smart Grid limitation for buffering is only possible if a Smart Grid is installed and
Recommended on mode is active.
You can combine Recommended on mode capacity limitation with other power
consumption controls. If you do so, the unit uses the most restrictive control.
INFORMATION
In case Smart Grid Forced off mode is active, the outdoor unit compressor and
electrical heaters will NOT operate.
Setup and configuration
See
"9.3.10  To connect a Smart
4
supply" [
 209].
You can connect one external temperature sensor. It measures the indoor or
outdoor ambient temperature. We recommend to use an external temperature
sensor in the following cases:
Indoor ambient temperature
In room thermostat control, the dedicated Human Comfort Interface (BRC1HHDA
used as room thermostat) measures the indoor ambient temperature. Therefore,
the Human Comfort Interface must be installed on a location:
-
Where the average temperature in the room can be detected
-
That is NOT exposed to direct sunlight
-
That is NOT near a heat source
-
That is NOT affected by outside air or air draught because of, for example, door
opening/closing
If this is NOT possible, we recommend to connect a remote indoor sensor (option
KRCS01-1).
Setup: For installation instructions, see the installation manual of the remote
indoor sensor, and the addendum book for optional equipment.
Configuration: Select room sensor [9.B].
Outdoor ambient temperature
In the outdoor unit, the outdoor ambient temperature is measured. Therefore,
the outdoor unit must be installed on a location:
-
At the north side of the house or at the side of the house where the most heat
emitters are located
-
That is NOT exposed to direct sunlight
If this is NOT possible, we recommend to connect a remote outdoor sensor
(option EKRSCA1).
4
control" [
 212]):
4
Grid"  [
  124] and
"Benefit kWh power
ERLA11~16D + EBVZ16S18+23D
Daikin Altherma 3 R F
4P643604-1B – 2022.05