Daikin EBVZ-D9W Installer's Reference Manual page 285

Table of Contents

Advertisement

Field settings table
Breadcrumb
Field code
Setting name
9.A.1
[D-08]
Electricity meter 1
9.A.2
[D-09]
Electricity meter 2 / PV meter
└─ Sensors
9.B.1
[C-08]
External sensor
9.B.2
[2-0B]
Ext. amb. sensor offset
9.B.3
[1-0A]
Averaging time
└─ Bivalent
9.C.1
[C-02]
Bivalent
9.C.2
[7-05]
Boiler efficiency
9.C.3
[C-03]
Temperature
9.C.4
[C-04]
Hysteresis
Installer settings
9.D
[C-09]
Alarm output
9.E
[3-00]
Auto restart
9.F
[E-08]
Power saving function
9.G
Disable protections
└─ Overview field settings
9.I
[0-00]
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
9.I
[0-01]
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
9.I
[0-02]
High ambient temp. for LWT add zone heating WD curve.
9.I
[0-03]
Low ambient temp. for LWT add zone heating WD curve.
9.I
[0-04]
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
9.I
[0-05]
Leaving water value for low ambient temp. for LWT add zone cooling WD curve.
9.I
[0-06]
High ambient temp. for LWT add zone cooling WD curve.
9.I
[0-07]
Low ambient temp. for LWT add zone cooling WD curve.
9.I
[0-0B]
Leaving water value for high ambient temp. for DHW WD curve.
9.I
[0-0C]
Leaving water value for low ambient temp. for DHW WD curve.
9.I
[0-0D]
High ambient temp. for DHW WD curve.
9.I
[0-0E]
Low ambient temp. for DHW WD curve.
9.I
[1-00]
Low ambient temp. for LWT main zone heating WD curve.
9.I
[1-01]
High ambient temp. for LWT main zone heating WD curve.
9.I
[1-02]
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
9.I
[1-03]
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
9.I
[1-04]
Weather dependent cooling of the main leaving water temperature zone.
9.I
[1-05]
Weather dependent cooling of the additional leaving water temperature zone
(*1) *6V_(*2) *9W_
(*3) *18*_(*4) *23*_
(*5) + EKHVCONV4
Range, step
Default value
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
6: 100 pulse/kWh (PV meter)
7: 1000 pulse/kWh (PV meter)
8: 1 pulse/m³ (gas meter)
9: 10 pulses/m³ (gas meter)
10: 100 pulses/m³ (gas meter)
R/W
0: No
1: Outdoor sensor
2: Room sensor
R/W
-5~5°C, step: 0,5°C
0°C
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
R/W
0: No
1: Bivalent through header
R/W
0: Very high
1: High
2: Medium
3: Low
4: Very low
R/W
-25~25°C, step: 1°C
0°C
R/W
2~10°C, step 1°C
3°C
R/W
0: Normally open
1: Normally closed
R/W
0: No
1: Yes
R/W
0: Disabled
1: Enabled
R/W
0: No
1: Yes
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
25°C
R/W
[9-05]~[9-06], step: 1°C
[2-0D]=0:
40°C
[2-0D]=1:
45°C
[2-0D]=2:
55°C
R/W
10~25°C, step: 1°C
15°C
R/W
-40~5°C, step: 1°C
-10°C
R/W
[9-07]~[9-08]°C, step: 1°C
[2-0D]=0:
18°C
[2-0D]=1:
5°C
[2-0D]=2:
18°C
R/W
[9-07]~[9-08]°C, step: 1°C
22°C
R/W
25~43°C, step: 1°C
35°C
R/W
10~25°C, step: 1°C
20°C
R/W
35~[6-0E]°C, step: 1°C
50°C
R/W
45~[6-0E]°C, step: 1°C
55°C
R/W
10~25°C, step: 1°C
15°C
R/W
-40~5°C, step: 1°C
-10°C
R/W
-40~5°C, step: 1°C
-10°C
R/W
10~25°C, step: 1°C
15°C
R/W
[9-01]~[9-00], step: 1°C
[2-0C]=0:
40°C
[2-0C]=1:
45°C
[2-0C]=2:
55°C
R/W
[9-01]~min(45, [9-00])°C, step: 1°C
25°C
R/W
0: Disabled
1: Enabled
R/W
0: Disabled
1: Enabled
7/12
Installer setting at variance with
default value
Date
Value
4P655202-1 - 2021.09