INFORMATION
If a heat pump failure occurs and Emergency is not set to Automatic (setting 1),
the room frost protection function and the underfloor heating screed dryout
function will remain active even if the user does NOT confirm emergency operation.
Compressor forced off
Compressor forced off mode can be activated to only allow the backup
heater to provide domestic hot water and space heating. When this mode is
activated:
Heat pump operation is NOT possible
Cooling is NOT possible
#
Code
[9.5.2]
[7-06]
Priorities
For systems with an integrated domestic hot water tank.
#
[9.6.1]
[5‑02]
[9.6.2]
[5‑03]
Activation of the Compressor forced off
mode:
0: disabled
1: enabled
Code
Space heating priority: Defines
whether backup heater will assist the heat
pump during domestic hot water operation.
For optimal operation and lowest power
consumption, it is strongly recommended to
keep the default setting (0).
If the backup heater operation is limited
([4‑00]=0) and the outdoor temperature is
lower than setting [5‑03], the domestic hot
water will not be heated with the backup
heater.
Priority temperature: Used for
calculation of anti-recycling timer. If [5‑02]=1, it
defines the outdoor temperature below which
the backup heater will assist during domestic
hot water heating.
[5‑01] Equilibrium temperature and [5‑03]
Space heating priority temperature are related
to backup heater. So, you must set [5‑03] equal
or a few degrees higher than [5‑01].
Description
Description
ERLA11~16D + EBVZ16S18+23D
Daikin Altherma 3 R F
4P643604-1B – 2022.05