7.1.2 Additional installation site requirements of the outdoor unit in cold climates

ERLA11~16D + EBVH/X11+16S18+23D
Daikin Altherma 3 R F
4P643602-1B – 2022.05
Install the outdoor unit away from direct sea winds.
Example: Behind the building.
a
If the outdoor unit is exposed to direct sea winds, install a windbreaker.
Height of windbreaker≥1.5×height of outdoor unit
Mind the service space requirements when installing the windbreaker.
a
d
c
a Sea wind
b Building
c Outdoor unit
d Windbreaker
The outdoor unit is designed for outdoor installation only, and for the following
ambient temperatures:
Cooling mode
Heating mode
DHW production
Protect the outdoor unit against direct snowfall and take care that the outdoor unit
is NEVER snowed up.
c
a Snow cover or shed
b Pedestal
c Prevailing wind direction
b
c
d
c
b
10~43°C
–25~35°C
–25~35°C
c
a
b
7
Unit installation
|
Installer reference guide
65