Daikin ERLA11D V3 Series Installer's Reference Manual page 230

Hide thumbs Also See for ERLA11D V3 Series:
Table of Contents

Advertisement

11
|
Configuration
Power saving function
Disable protections
Installer reference guide
230
Power saving function
NOTICE
Power saving function. If you want to use the power saving function, on the outdoor
unit PCB:
Disconnect X804A from X805A.
Connect X804A to X806A.
X806A
3N~
X805A
X805A
1N~
X806A
Defines whether the outdoor unit power supply can be interrupted (internally by
indoor unit control) during stand-still conditions (no space heating/cooling nor
domestic hot water demand). The final decision to allow power interruption of the
outdoor unit during standstill depends on the ambient temperature, compressor
conditions and minimum internal timers.
To enable the power saving function setting, [E‑08] needs to be enabled on the
user interface.
#
Code
[9.F]
[E‑08]
Protective functions
The unit is equipped with the following protective functions:
Room antifrost [2-06]
Tank disinfection [2-01]
INFORMATION
Protective functions – "Installer-on-site mode". The software is equipped with
protective functions, such as room antifrost. The unit automatically runs these
functions when necessary.
During installation or service this behaviour is undesired. Therefore, the protective
functions can be disabled:
At first power-on: The protective functions are disabled by default. After 12
hours they will be automatically enabled.
Afterwards: An installer can manually disable the protective functions by setting
[9.G]: Disable protections=Yes. After his work is done, he can enable the
protective functions by setting [9.G]: Disable protections=No.
X804A
X804A
Power saving function for outdoor unit:
0: No
1: Yes
Description
ERLA11~16D + EBVH/X11+16S18+23D
Daikin Altherma 3 R F
4P643602-1B – 2022.05