Daikin ERLA11D V3 Series Installer's Reference Manual page 274

Hide thumbs Also See for ERLA11D V3 Series:
Table of Contents

Advertisement

16
|
Disposal
Installer reference guide
274
#
Action
1
Start from the default situation.
2
Select mode 2.
Press and hold BS1 for 5 seconds.
3
Select setting 9.
Press BS2 9 times.
4
Select value 2.
a
Display the current value.
Press BS3 once.
b
Change the value to 2.
Press BS2 once.
c
Enter the value in the system.
Press BS3 once.
d
Confirm.
Press BS3 once.
5
Return to the default situation.
Press BS1 once.
(a)
= OFF,
= ON, and
Result: The recovery mode is activated. The unit opens the electronic expansion
valves.
To deactivate the recovery mode
After recovering refrigerant, deactivate the recovery mode as follows:
#
Procedure
1
Start from the default situation.
2
Select mode 2.
Press and hold BS1 for 5 seconds.
3
Select setting 9.
Press BS2 9 times.
4
Select value 1.
= flashing.
(a)
7-segments display
(a)
7-segments display
ERLA11~16D + EBVH/X11+16S18+23D
Daikin Altherma 3 R F
4P643602-1B – 2022.05