Daikin ERLA11D V3 Series Installer's Reference Manual page 300

Hide thumbs Also See for ERLA11D V3 Series:
Table of Contents

Advertisement

10/13
Field settings table
Breadcrumb Field code
Setting name
9.I
[6-09]
--
9.I
[6-0A]
What is the desired comfort storage temperature?
9.I
[6-0B]
What is the desired eco storage temperature?
9.I
[6-0C]
What is the desired reheat temperature?
9.I
[6-0D]
What is the desired DHW production type?
9.I
[6-0E]
What is the maximum DHW temperature setpoint?
9.I
[7-00]
Domestic hot water booster heater overshoot temperature.
9.I
[7-01]
Domestic hot water booster heater hysteresis.
9.I
[7-02]
How many leaving water temperature zones are there?
9.I
[7-03]
--
9.I
[7-04]
--
9.I
[7-05]
Boiler efficiency
9.I
[7-06]
Compressor forced off
9.I
[7-07]
BBR16 activation
9.I
[7-08]
DHW stratification
9.I
[7-09]
Settable lower limit for the PWM of the pump
9.I
[7-0A]
Additional zone fixed pump PWM, in case a bizone kit is installed.
9.I
[7-0B]
Main zone fixed pump PWM, in case a bizone kit is installed.
9.I
[7-0C]
Time needed by the mixing valve to turn from one side to the other, in case a
bizone kit is installed.
9.I
[7-0D]
--
9.I
[7-0E]
--
9.I
[8-00]
Minimum running time for domestic hot water operation.
9.I
[8-01]
Maximum running time for domestic hot water operation.
9.I
[8-02]
Anti-recycling time.
9.I
[8-03]
Booster heater delay timer.
9.I
[8-04]
Additional running time for the maximum running time.
9.I
[8-05]
Allow modulation of the LWT to control the room temp?
9.I
[8-06]
Leaving water temperature maximum modulation.
9.I
[8-07]
What is the desired comfort main LWT in cooling?
9.I
[8-08]
What is the desired eco main LWT in cooling?
9.I
[8-09]
What is the desired comfort main LWT in heating?
9.I
[8-0A]
What is the desired eco main LWT in heating?
9.I
[8-0B]
--
9.I
[8-0C]
--
9.I
[8-0D]
--
9.I
[9-00]
What is the maximum desired LWT for main zone in heating?
9.I
[9-01]
What is the mimimum desired LWT for main zone in heating?
9.I
[9-02]
What is the maximum desired LWT for main zone in cooling?
9.I
[9-03]
What is the mimimum desired LWT for main zone in cooling?
9.I
[9-04]
Leaving water temperature overshoot temperature.
9.I
[9-05]
What is the mimimum desired LWT for add. zone in heating?
9.I
[9-06]
What is the maximum desired LWT for add. zone in heating?
9.I
[9-07]
What is the mimimum desired LWT for add. zone in cooling?
4P655201-1 - 2021.09
Range, step
Default value
0
R/W
30~[6-0E]°C, step: 1°C
55°C
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
R/W
0: Reheat only
1: Reheat + sched.
2: Scheduled only
R/W
[E-07]=0 or 7 (*3):
40~60°C, step: 1°C
60°C
[E-07]=1 (*4):
40~65°C, step: 1°C
60°C
[E-07]=3 or 8 (*3):
40~75°C, step: 1°C
75°C
[E-07]=5 (*3):
40~80°C, step: 1°C
80°C
R/W
0~4°C, step: 1°C
0°C
R/W
2~40°C, step: 1°C
2°C
R/W
0: Single zone
1: Dual zone
2.5
0
R/W
0: Very high
1: High
2: Medium
3: Low
4: Very low
R/W
0: Disabled
1: Enabled
R/W
0: Disabled
1: Enabled
R/O (*3)
0: Disabled (*3)
R/W (*4)
1: Enabled (*4)
R/W
20
R/W
20~95%, step 5%
95%
R/W
20~95%, step 5%
95%
R/W
20~300 seconds, step 5 sec
125 seconds
4
7
R/O
0~20 min, step 1 min
1 min
R/W
5~95 min, step: 5 min
30 min
R/W
0~10 hour, step: 0,5 hour
3 hour
R/W
20~95 min, step: 5 min
50 min
R/W
0~95 min, step: 5 min
95 min
R/W
0: No
1: Yes
R/W
0~10°C, step: 1°C
5°C
R/W
[9-03]~[9-02], step: 1°C
18°C
R/W
[9-03]~[9-02], step: 1°C
20°C
R/W
[9-01]~[9-00], step: 1°C
35°C
R/W
[9-01]~[9-00], step: 1°C
33°C
13
10
16
R/W
[2-0C]=2:
37~60, step: 1°C
60°C
[2-0C]≠2:
37~55, step: 1°C
55°C
R/W
15~37°C, step: 1°C
25°C
R/W
18~22°C, step: 1°C
22°C
R/W
5~18°C, step: 1°C
7°C
R/W
1~4°C, step: 1°C
2°C
R/W
15~37°C, step: 1°C
25°C
R/W
[2-0D]=2:
37~60, step: 1°C
60°C
[2-0D]≠2:
37~55, step: 1°C
55°C
R/W
5~18°C, step: 1°C
7°C
(*1) *6V_(*2) *9W_(*3) EBB*_(*4) EBV*_
Installer setting at variance with
default value
Date
Value
(*5) *X*_(*6) *H*_(*7) *11*_(*8) *16*_
(*9) *SU*_(*10) *18*_(*11) *23*