8.6.4 To connect the recirculation piping

8.6.5 To fill the water circuit

ERLA11~16D + EBVH/X11+16S18+23D
Daikin Altherma 3 R F
4P643602-1B – 2022.05
NOTICE
Overpressure bypass valve (delivered as accessory). We recommend to install the
overpressure bypass valve in the space heating water circuit.
Mind the minimum water volume when choosing the installation location of the
overpressure bypass valve (at the indoor unit, or at the collector). See
check the water volume and flow
Mind the minimum flow rate when adjusting the overpressure bypass valve
setting. See
"12.4.1 Minimum flow
NOTICE
Install air purge valves at all local high points.
Prerequisite: Only required if you need recirculation in your system.
1 Remove the top panel from the unit, see
4
unit" [
 77].
2 Cut out the rubber grommet on top of the unit, and remove the stop. The
recirculation connector is placed below the hole.
3 Route the recirculation piping through the grommet and connect it to the
recirculation connector.
4 Reattach the top panel.
To fill the water circuit, use a field supply filling kit. Make sure you comply with the
applicable legislation.
NOTICE
Pump. To prevent blocking of the pump rotor, commission the unit as quickly as
possible after filling the water circuit.
INFORMATION
Make sure both air purge valves (one on the magnetic filter and one on the backup
heater) are open.
rate" [
4
 105].
"8.5.3  To check the water volume and flow
4
rate" [
 242].
8
Piping installation
|
"8.5.3 To
4
rate"  [
  105] and
"7.2.4  To open the indoor
Installer reference guide
111