Field settings table
Breadcrumb Field code
Setting name
9.1.4.1
[5-0D]
Voltage
9.1.4.2
[4-0A]
Configuration
9.1.4.3
[6-03]
Capacity step 1
9.1.4.4
[6-04]
Additional capacity step 2
└─ Main zone
9.1.5.1
[2-0C]
Emitter type
9.1.5.2
[C-07]
Control
9.1.5.3
Setpoint mode
9.1.5.4
Schedule
9.1.5.5
WD curve type
9.1.6
[1-00]
Low ambient temp. for LWT main zone heating WD curve.
9.1.6
[1-01]
High ambient temp. for LWT main zone heating WD curve.
9.1.6
[1-02]
Leaving water value for low ambient temp. for LWT main zone heating WD curve.
9.1.6
[1-03]
Leaving water value for high ambient temp. for LWT main zone heating WD curve.
9.1.7
[1-06]
Low ambient temp. for LWT main zone cooling WD curve.
9.1.7
[1-07]
High ambient temp. for LWT main zone cooling WD curve.
9.1.7
[1-08]
Leaving water value for low ambient temp. for LWT main zone cooling WD curve.
9.1.7
[1-09]
Leaving water value for high ambient temp. for LWT main zone cooling WD curve.
└─ Additional zone
9.1.8.1
[2-0D]
Emitter type
9.1.8.3
Setpoint mode
9.1.8.4
Schedule
9.1.9
[0-00]
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
9.1.9
[0-01]
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
9.1.9
[0-02]
High ambient temp. for LWT add zone heating WD curve.
9.1.9
[0-03]
Low ambient temp. for LWT add zone heating WD curve.
9.1.A
[0-04]
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
9.1.A
[0-05]
Leaving water value for low ambient temp. for LWT add zone cooling WD curve.
9.1.A
[0-06]
High ambient temp. for LWT add zone cooling WD curve.
9.1.A
[0-07]
Low ambient temp. for LWT add zone cooling WD curve.
└─ Tank
9.1.B.1
[6-0D]
Heat up mode
9.1.B.2
[6-0A]
Comfort setpoint
9.1.B.3
[6-0B]
Eco setpoint
9.1.B.4
[6-0C]
Reheat setpoint
9.1.B.6
[6-08]
Reheat hysteresis
└─ Domestic hot water
(*1) *6V_(*2) *9W_(*3) EBB*_(*4) EBV*_
(*5) *X*_(*6) *H*_(*7) *11*_(*8) *16*_
(*9) *SU*_(*10) *18*_(*11) *23*
Range, step
Default value
R/W (*1)
0: 230V, 1~ (*1)
R/O (*2)
1: 230V, 3~ (*1)
2: 400V, 3~ (*2)
R/W
0: 1
1: 1/1+2
2: 1/2
3: 1/2 + 1/1+2 in emergency
R/W
0~10kW, step: 0,2kW
2kW (*1)
3kW (*2)
R/W
0~10kW, step: 0,2kW
4kW (*1)
6kW (*2)
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
R/W
0: LWT control
1: Ext RT control
2: RT control
R/W
0: Fixed
1: WD heating, fixed cooling
2: Weather dependent
R/W
0: No
1: Yes
R/W
0: 2-points
1: Slope-Offset
R/W
-40~5°C, step: 1°C
-10°C
R/W
10~25°C, step: 1°C
15°C
R/W
[9-01]~[9-00], step: 1°C
[2-0C]=0:
40°C
[2-0C]=1:
45°C
[2-0C]=2:
55°C
R/W
[9-01]~min(45, [9-00])°C, step: 1°C
25°C
R/W
10~25°C, step: 1°C
20°C
R/W
25~43°C, step: 1°C
35°C
R/W
[9-03]~[9-02]°C, step: 1°C
22°C
R/W
[9-03]~[9-02]°C, step: 1°C
[2-0C]=0:
18°C
[2-0C]=1:
5°C
[2-0C]=2:
18°C
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
R/W
0: Fixed
1: WD heating, fixed cooling
2: Weather dependent
R/W
0: No
1: Yes
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
25°C
R/W
[9-05]~[9-06], step: 1°C
[2-0D]=0:
40°C
[2-0D]=1:
45°C
[2-0D]=2:
55°C
R/W
10~25°C, step: 1°C
15°C
R/W
-40~5°C, step: 1°C
-10°C
R/W
[9-07]~[9-08]°C, step: 1°C
[2-0D]=0:
18°C
[2-0D]=1:
5°C
[2-0D]=2:
18°C
R/W
[9-07]~[9-08]°C, step: 1°C
22°C
R/W
25~43°C, step: 1°C
35°C
R/W
10~25°C, step: 1°C
20°C
R/W
0: Reheat only
1: Reheat + sched.
2: Scheduled only
R/W
30~[6-0E]°C, step: 1°C
55°C
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
R/W
2~20°C, step: 1°C
10°C
5/13
Installer setting at variance with
default value
Date
Value
4P655201-1 - 2021.09