Glycol. For safety reasons, it is NOT allowed to add any kind of glycol to the
water circuit.
Piping length. It is recommended to avoid long runs of piping between the
domestic hot water tank and the hot water end point (shower, bath,...) and to
avoid dead ends.
Piping diameter. Select the water piping diameter in relation to the required
water flow and the available external static pressure of the pump. See
4
"17 Technical
data" [
unit.
Water flow. You can find the minimum required water flow for indoor unit
operation in the following table. In all cases, this flow needs to be guaranteed.
When the flow is lower, the indoor unit will stop operation and display error 7H.
If operation is...
Cooling
Heating/defrost
Domestic hot water production
Field supply components – Water. Only use materials that are compatible with
water used in the system and with the materials used in the indoor unit.
Field supply components – Water pressure and temperature. Check that all
components in the field piping can withstand the water pressure and water
temperature.
Water pressure – Domestic hot water. The maximum water pressure is 10 bar
(=1.0  MPa), and must be in accordance with the applicable legislation. Provide
adequate safeguards in the water circuit to ensure that the maximum pressure is
NOT exceeded (see
"8.6.3 To connect the water
water pressure to operate is 1 bar (=0.1 MPa).
Water pressure – Space heating/cooling circuit. The maximum water pressure is
3 bar (=0.3 MPa). Provide adequate safeguards in the water circuit to ensure that
the maximum pressure is NOT exceeded. The minimum water pressure to
operate is 1 bar (=0.1 MPa).
Water temperature. All installed piping and piping accessories (valve,
connections,...) MUST withstand the following temperatures:
INFORMATION
The following figure is an example and may NOT completely match your system
layout
 278] for the external static pressure curves of the indoor
Then the minimum required flow rate
8
Piping installation
|
is...
16 l/min
22 l/min
4
piping" [
 109]). The minimum