If stranded conductor wires are used, install a round crimp-style terminal on the
end of the wire. Place the round crimp-style terminal on the wire up to the
covered part and fasten the terminal with the appropriate tool.
b
a
a Stranded conductor wire
b Round crimp-style terminal
Use the following methods for installing wires:
Wire type
Single-core wire
Stranded conductor wire
with round crimp-style
terminal
Tightening torques
Outdoor unit:
Item
M4 (X1M)
M4 (earth)
M5 (X1M)
M5 (earth)
Indoor unit:
Item
X1M
X2M
X5M
X6M
X10M
9
Installation method
c b
A
c
a
a Curled single-core wire
b Screw
c Flat washer
c b
B
B
a
a Terminal
b Screw
c Flat washer
Allowed
NOT allowed
Tightening torque (N•m)
Tightening torque (N•m)
Electrical installation
|
AA´
a
a
b
c
1.2~1.8
1.2~1.4
2.0~3.0
2.4~2.9
2.45 ±10%
0.88 ±10%
0.88 ±10%
2.45 ±10%
0.88 ±10%