9
|
Electrical installation
Installer reference guide
122
Item
Remote outdoor sensor
Remote indoor sensor
Human Comfort Interface
LAN adapter
WLAN cartridge
Description
See:
Installation manual of the remote outdoor
sensor
Addendum book for optional equipment
Wires: 2×0.75 mm²
[9.B.1]=1 (External sensor = Outdoor)
[9.B.2] Ext. amb. sensor offset
[9.B.3] Averaging time
See:
Installation manual of the remote indoor
sensor
Addendum book for optional equipment
Wires: 2×0.75 mm²
[9.B.1]=2 (External sensor = Room)
[1.7] Room sensor offset
See:
Installation and operation manual of the
Human Comfort Interface
Addendum book for optional equipment
Wires: 2×(0.75~1.25 mm²)
Maximum length: 500 m
[2.9] Control
[1.6] Room sensor offset
See:
Installation manual of the LAN adapter
Addendum book for optional equipment
Wires: 2×(0.75~1.25 mm²). Must be
sheathed.
Maximum length: 200 m
See installation manual of the LAN adapter
See:
Installation manual of the WLAN cartridge
Installer reference guide
[D] Wireless gateway
ERLA11~16D + EBVH/X11+16S18+23D
Daikin Altherma 3 R F
4P643602-1B – 2022.05