A-8-2 Changing The Unit Operation Settings For Multiple Nx Units - Omron sysmac NX102-9 Series Owner's Manual

Machine automation controller, cpu unit built-in ethernet/iptm port
Table of Contents

Advertisement

Appendices
A-8-2
Changing the Unit Operation Settings for Multiple NX Units
Change the Unit operation settings for multiple NX Units mounted to the Controller. In this example, the
unit numbers of the relevant NX Units are 1 and 2.
The following table gives the setting procedure.
Procedure
number
1
Change the parameter write
mode of the NX Unit with unit
number 1 to Write mode.
2
Change the parameter write
mode of the NX Unit with unit
number 2 to Write mode.
3
Write values to the NX object of
the NX Unit with unit number 1.
4
Write values to the NX object of
the NX Unit with unit number 2.
5
Save the values that were set in
the NX Unit with unit number 1.
6
Save the values that were set in
the NX Unit with unit number 2.
7
Restart the NX Unit with unit
number 1.
8
Restart the NX Unit with unit
number 2.
A-70
Description
0x74
NX Configuration
object
0x74
NX Configuration
object
0x74
NX Configuration
object
0x74
NX Configuration
object
0x74
NX Configuration
object
0x74
NX Configuration
object
0x74
NX Configuration
object
0x74
NX Configuration
object
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User's Manual (W506)
Used CIP object
Instance
Class ID
ID
0x01
0x37
Switch parameter
write mode
0x01
0x37
Switch parameter
write mode
0x01
0x34
Write NX object
0x01
0x34
Write NX object
0x01
0x36
Save parameter
0x01
0x36
Save parameter
0x01
0x35
Restart NX unit
0x01
0x35
Restart NX unit
Unit
Service code
number
0x01
0x02
0x01
0x02
0x01
0x02
0x01
0x02