7 Tag Data Link Functions

7-2-11 Verifying the Tag Data Links

Tag data link parameters (such as the tag set settings and connection settings) can be compared with
the parameters of the built-in EtherNet/IP ports in the EtherNet/IP network. The following procedure
shows how to compare the parameters. For details on how to connect to the network from the Network
Configurator, refer to 7-2-8 Connecting the Network Configurator to the Network.
Precautions for Correct Use
Precautions for Correct Use
Make sure that the major CIP revision of the device registered with the Network Configurator is
the same as the major CIP revision of the NJ/NX-series CPU Unit that you use. If the major CIP
revisions are not the same, the parameters may not be compared. To determine whether com-
parison is possible, refer to 7-2-3 Registering Devices.
Verifying the Network Configuration
You can use the following procedure to compare the list of registered devices in the Network Configura-
tion Pane with the devices connected on the EtherNet/IP network, and check the IP addresses and
device types. This function does not verify device parameters.
1
Connect the Network Configurator online.
2
Select Network - Verify Structure.
The following progress monitor is displayed to show the progress as data is read from the net-
work and compared.
3
The results of the comparison between the network configuration file and data from the network
are displayed as shown below.
Differences Not Found in the Comparison
7-66
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User's Manual (W506)