Omron sysmac NX102-9 Series Owner's Manual page 241

Machine automation controller, cpu unit built-in ethernet/iptm port
Table of Contents

Advertisement

Yes Button:
The following dialog box is displayed.
Select the Initialize tag data link configuration, and then emulate cycling power Option and then click
the OK Button.
Precautions for Correct Use
Precautions for Correct Use
The Controller is not restarted. Only the built-in EtherNet/IP port is reset.
No Button:
The tag data link settings will not be cleared and the built-in EtherNet/IP port will not be reset.
Additional Information
You can also execute the Reset service of the Identity object for the CPU Unit to clear the tag
data link settings. The procedures to execute the service from the Network Configurator is given
below.
(1) Connect the Network Configurator to the network.
(2) Select Tool - Setup Parameters on the main window.
Then the dialog box for the general parameter settings are displayed.
(3) Specify the target device and message to send.
•Target Node Address: Enter the IP address of the target device.
•Service:Select Reset.
•Class:Enter 01.
•Instance:Enter 01.
•Attribute:Enter 00.
•Data:Enter 02.*
(4) Click the Send Button.
*For a CPU Unit version 1.09 or earlier, specify 01.
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User's Manual (W506)
7 Tag Data Link Functions
7
7-73