Clearances - Empire Comfort Systems DVLXG75BP90N-1 Installer's Manual

Direct vent zero clearance gas fireplace heater
Table of Contents

Advertisement

Clearance to Combustibles
Back
Side
Floor
Top Stand-Off Bracket
Top Framing Edge
NOTE: COMBUSTIBLE MATERIALS ALLOWED IN SHADED AREA
Vent Pipe Clearance
NOTICE: Horizontal vent, maintain a minimum 1-inch clearance
to the bottom and sides of the vent, and
clearance to combustibles above the vent pipe.
Side Wall and Ceiling
The minimum clearance from the top of fire place to the ceiling is
36 inches. The minimum clearance from the side of the fireplace
opening to an adjacent sidewall is 6 inches.

CLEARANCES

ZERO
ZERO
ZERO
ZERO
ZERO
3-inch
minimum
Mantel and TV Clearances
The minimum mantel and TV clearances are shown in the
diagrams below.
A
COMBUSTIBLE MANTELS &
TVs CAN BE INSTALLED
ANYWHERE IN THIS ZONE
B
C
D
E
45°
10"
F
MANTEL
G
8"
8"
TOP EDGE OF
TOP EDGE OF
FIREPLACE OPENING
FIREPLACE OPENING
Depth
A
16"
B
15"
C
14"
D
13"
E
12"
F
11"
G
10"
3" Minimum
Height
14"
13"
12"
11"
10"
9"
8"