Clearances - Empire Comfort Systems VFP36SP32E Installation Instructions And Owner's Manual

Premium vent-free multi-sided fireplaces
Table of Contents

Advertisement

Sidewall Clearances: The clearance from the inside of the fireplace
to perpendicular combustible side wall should not be less than
1 3/4". See Figures 4a and 4b.
36"
MIN.
Figure 4a - See Through Fireplace Clearances
36"
MIN.
Figure 4b - Peninsula Fireplace Clearances
39813-1-0919

CLEARANCES

1 3/4" MIN.
PERPENDICULAR
COMBUSTIBLE
(CEILING TO
SIDEWALL
TOP OF HOOD)
1 3/4" MIN.
PERPENDICULAR
(CEILING TO
COMBUSTIBLE
TOP OF HOOD)
SIDEWALL
Combustible material clearance from front of firebox: 36"
minimum
Fireplace Side and Back Clearances: The fireplace outer casing
side(s) require a minimum 1/2" clearance to combustibles.
Top Framing and Finishing: Combustible framing may rest on
top of standoffs. Combustible finishing materials may extend to
the top standoff screws on the front edge of the top outer wrap.
See Figure 5.
42"
MIN.
2 X 4
HEADER
TOP OUTER
WRAP
42"
MIN.
COMBUSTIBLE
FINISHED WALL
OR MANTEL
FINISH WITH TRIM KIT
OR NON-COMBUSTIBLE
MATERIAL AS DESIRED.
STANDOFF
FIREBOX
Figure 5