Forced Cooling Operation

2. Forced Cooling Operation

Conditions
Start
Command
frequency
End
Others
Indoor Unit
Outdoor Unit
Trial Operation and Field Settings
Item
The forced cooling operation is allowed when both the following conditions are
met.
1) The outdoor unit is not abnormal and not in the 3-minute standby mode.
2) The outdoor unit is not operating.
The forced cooling operation starts when any of the following conditions is
fulfilled.
1) Press the forced cooling operation ON/OFF button (SW1) on the indoor unit
for 5 seconds.
2) Press the forced cooling operation ON/OFF button (SW1) on the outdoor
unit.
55 Hz
The forced cooling operation ends when any of the following conditions is
fulfilled.
1) The operation ends automatically after 15 minutes.
2) Press the forced cooling operation ON/OFF button (SW1) on the indoor unit
again.
3) Press the ON/OFF button on the remote controller.
4) Press the forced cooling operation ON/OFF button (SW1) on the outdoor
unit.
The protection functions are prior to all others in the forced cooling operation.