Troubleshooting
4.21 Radiation Fin Temperature Rise
L4
Remote
Controller
Display
Method of
A radiation fin temperature rise is detected by checking the radiation fin thermistor with the
Malfunction
compressor on.
Detection
If the radiation fin temperature with the compressor on is above A.
Malfunction
The error is cleared when the radiation fin temperature drops below B.
Decision
If the error repeats, the system is shut down.
Conditions
Reset condition: Continuous run for about 60 minutes without any other error
Defective outdoor fan motor
Supposed
Short circuit
Causes
Defective radiation fin thermistor
Disconnection of connector
Defective outdoor unit PCB
Silicon grease is not applied properly on the radiation fin after replacing the outdoor unit PCB.
Service Diagnosis
A
105°C (221°F)
B
97°C (206.6°F)
SiUS04-924_A