Dc Fan Lock - Daikin H Series Service Manual

Inverter pair wall mounted type
Hide thumbs Also See for H Series:
Table of Contents

Advertisement

SiUS04-924_A

4.11 DC Fan Lock

E7
Remote
Controller
Display
Method of
An error is determined with the high-voltage fan motor rotation speed detected by the Hall IC.
Malfunction
Detection
 The fan does not start in 15 ~ 60 seconds even when the fan motor is running.
Malfunction
 If the error repeats, the system is shut down.
Decision
 Reset condition: Continuous run for about 5 minutes without any other error
Conditions
 Disconnection of fan motor
Supposed
 Foreign matters stuck in the fan
Causes
 Defective fan motor
 Defective outdoor unit PCB
Troubleshooting
Check No.16
Refer to P.116
84
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Fan motor connector
disconnected?
NO
Foreign matters in or
around the fan?
NO
Turn on the power.
Rotate the fan.
Fan rotates
smoothly?
YES
Check No. 16
Check the rotation pulse input on
the outdoor unit PCB.
Pulse signal generated?
YES
YES
YES
NO
NO
Troubleshooting
Turn off the power and
reconnect the connector.
Remove them.
Replace the outdoor fan
motor.
Replace the outdoor fan
motor.
Replace the outdoor unit
PCB.
(R14410)
Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents