Troubleshooting
4.17 Position Sensor Abnormality
H6
Remote
Controller
Display
Method of
A compressor start-up failure is detected by checking the compressor running condition through the
Malfunction
position detection circuit.
Detection
If the error repeats, the system is shut down.
Malfunction
Reset condition: Continuous run for about 5 minutes without any other error
Decision
Conditions
Disconnection of compressor relay harness
Supposed
Defective compressor
Causes
Defective outdoor unit PCB
Start-up failure caused by the closed stop valve
Input voltage is out of specification
Service Diagnosis
SiUS04-924_A
93