Indoor Unit; Removal Of Air Filters / Front Panel - Daikin H Series Service Manual

Inverter pair wall mounted type
Hide thumbs Also See for H Series:
Table of Contents

Advertisement

Indoor Unit

1. Indoor Unit

1.1

Removal of Air Filters / Front Panel

Procedure
Step
1. Features
2. Remove the air filters.
1
Open the front panel to
the position where it
stops.
2
Slightly push up the
center knob of the air
filter and unfasten the
hooks.
3
Pull out the air filter
downward and remove
it.
Removal Procedure
Warning
Be sure to wait for 10 minutes or more after turning off all power supplies
before disassembling work.
Procedure
Signal receiver
TIMER lamp
INVERTER
ON/OFF
ON/OFF button
Room temperature thermistor
Air filter
(R9473)
Operation lamp
INTELLIGENT
EYE sensor
INTELLIGENT
EYE lamp
(R9474)
Front Panel
(R9475)
Hook
(R13625)
SiUS04-924_A
Points
Warning
Dangerous: High voltage
A high voltage is applied to all
the electric circuits of this
product including thermistors.
 When the signal receiver
catches a signal from the
remote controller, the receiving
tone sounds and the operation
lamp blinks immediately to
confirm the signal reception.
 When the ON/OFF button is
kept pressed for 5 seconds, the
forced cooling operation is
performed for about 15 minutes.
 The 3 filters are
interchangeable.
 The air filter can be set easily by
inserting it along the guides.
 Insert the air filter with the
"FRONT" mark faced up.
 Be sure to insert the hooks (at 2
lower positions) when
reassembling the air filter.