Check
5.9

Installation Condition Check

Check No.17
Service Diagnosis

Installation condition check

Check the allowable
dimensions of the air
suction and
discharge area.
OK
Is the discharged
air short-circuited?
NO
Is the outdoor heat
exchanger very dirty?
NO
Is the airflow blocked by
obstacles or winds
blowing in the opposite
direction?
NO
NG
YES
YES
YES
SiUS04-924_A
Change the installation
location or direction.
Change the installation
location or direction.
Clean the outdoor
heat exchanger.
Change the installation
location or direction.
Check the outdoor temperature.
(The outdoor temperature
should be 46˚C (114.8˚F) or
lower.)
(R14468)
117