2. Forced Cooling Operation
Outline
The forced cooling operation is allowed when both the following conditions are met.
1. The outdoor unit is not abnormal and not in the 3-minute standby mode.
2. The outdoor unit is not operating.
Protection functions have priority over all other functions during forced cooling operation.
Details
With indoor unit ON/OFF switch
Press indoor unit ON/OFF switch for at least 5 seconds. The operation will start.
Forced cooling operation will stop automatically after about 15 minutes.
To stop the operation, press indoor unit ON/OFF switch.
Part 7 Trial Operation and Field Settings
Forced Cooling Operation
ON/OFF switch
R4003873