Troubleshooting
4.15 High Pressure Control in Cooling
F6
Remote
Controller
Display
Method of
High-pressure control (operation halt, frequency drop, etc.) is activated in cooling operation if the
Malfunction
temperature sensed by the outdoor heat exchanger thermistor exceeds the limit.
Detection
The temperature sensed by the outdoor heat exchanger thermistor rises above about 65°C
Malfunction
Decision
The error is cleared when the temperature drops below about 50°C (122°F).
Conditions
The installation space is not large enough.
Supposed
Dirty outdoor heat exchanger
Causes
Defective outdoor fan motor
Defective stop valve
Defective electronic expansion valve or coil
Defective outdoor heat exchanger thermistor
Defective outdoor unit PCB
Service Diagnosis
(149°F).
SiUS04-924_A
89