Forced Cooling Operation Mode

2. Forced Cooling Operation Mode
Outline
Forced operation mode includes only forced cooling.
Detail
Conditions
Start
Command
frequency
End
Others
289
Item
1) The outdoor unit is not abnormal and not in the 3-minute standby mode.
2) The outdoor unit is not operating.
The forced cooling operation is allowed when the above both conditions are
met.
1) Press the forced cooling operation ON/OFF button (SW1) on the indoor unit
for 5 seconds.
2) Press the forced cooling operation ON/OFF button (SW1) on the outdoor
unit.
RK(X)S20-35G2V1B, ARXS20-35G2V1B: 68 Hz
RK(X)S20-35G2V1B9, ARXS20-35G3V1B: 58 Hz
RK(X)S42G2V1B, ARXS42G2V1B: 47 Hz
RK(X)S50G2V1B, ARXS50G2V1B: 66 Hz
1) The operation ends automatically after 15 minutes.
2) Press the forced cooling operation ON/OFF button (SW1) on the indoor unit
again.
3) Press the ON/OFF button on the remote controller.
4) Press the forced cooling operation ON/OFF button (SW1) on the outdoor
unit.
The protection functions are prior to all others in the forced cooling operation.
Indoor Unit
Outdoor Unit
(RK(X)S 20/25/35G2V1B, ARXS20/25/35G2V1B)
(SW1)
Forced Cooling
ON/OFF button (SW1)