Switching Over Internal/External Set Point - Samson TROVIS 6495-2 Mounting And Operating Instructions

Industrial controller
Hide thumbs Also See for TROVIS 6495-2:
Table of Contents

Advertisement

The current value of the reset time is
highlighted: 120 s.
... Keep pressed and change the reset
time TN to 100 s.
1x Confirm the reset time.
Return to the operating level
3x Return to the operating level.
8.3.3
Switching over internal/
external set point
If the external set point SPE (C.2.1.2-1) is
configured, the set point SP is equal to SPE.
The switchover to an internal set point SPI is
performed in the operating menu.
The controller is currently in the operating
level:
EB 6495-2 EN
Î Enter the operating menu (see sec-
tion 8.3.1).
Switchover to the internal set point SPI
1x Select Set point menu item.
1x Activate Set point menu item.
The current set point is displayed: SP =
SPE.
1x Activate the set point SP.
The current set point is highlighted:
SPE.
1x Select internal set point SPI.
1x Confirm setting.
SPI is now the active set point.