O.1
Analog output AO1
O.1.5
Limit output rate <O.1.1≠0, O.1.4-0>
-0 Off
-1 Increasing, continuously active
-2 Decreasing, continuously active
-3 Increasing and decreasing
-4 Increasing. Start with DI1
-5 Increasing. Start with DI2
-6 Increasing. Start with DI3
-7 Increasing. Start with DI4
-8 Decreasing. Start with DI1
-9 Decreasing. Start with DI2
-10 Decreasing. Start with DI3
-11 Decreasing. Start with DI4
AO1.GD1 Gradient for increasing output signal
<O.1.5-1/-3/-4/-5/-6/-7>
AO1.GD2 Gradient for decreasing output signal
<O.1.5-2/-3/-8/-9/-10/-11>
AO1.TB2
Time base <O.1.5≠0>
O.1.6
Constant output value 1 with DI (auto mode) <O.1.1≠0>
-0 Off
-1 With digital input DI1
-2 With digital input DI2
-3 With digital input DI3
-4 With digital input DI4
AO1.K1
Constant output value 1 <O.1.6≠0>
O.1.7
Constant output value 2 with DI (man/auto) <O.1.1≠0>
-0 Off
-1 With digital input DI1
-2 With digital input DI2
-3 With digital input DI3
-4 With digital input DI4
AO1.K2
Constant output value 2 <O.1.7≠0>
O.1.8
Limit output by input TR <O.1.1≠0>
-0 Off
-1 To minimum value
-2 To maximum value
EB 6495-2 EN
Annex A (configuration guide)
[0.1 ... 100.0 %]
[0.1 ... 100.0 %]
[s, min, h]
[–10.0 ... 110.0 %]
[–10.0 ... 110.0 %]
Default
Setting
setting
O.1.5-0
1.0 %
1.0 %
s
O.1.6-0
0.0 %
O.1.7-0
0.0 %
O.1.8-0
16-47