7 Start-up and configuration

The work described in this section is only to
be performed by personnel appropriately
qualified to carry out such tasks.
Before start-up, make sure the following con-
ditions are met:
− The industrial controller is properly
mounted according to the instructions.
− The electrical connection is properly per-
formed.
After applying the supply voltage, the indus-
trial controller is ready for use.
Î A calibration of the analog inputs and
outputs can compensate for long lines,
small wire cross-sections or tolerances of
measuring transducers and final control
elements (see the 'Operation' section).

7.1 Configuration

The controller is configured in the configura-
tion menu. In the configuration menu, the
controller is adapted to its control task by
changing individual configuration items and
parameters.
The configuration menu is subdivided into
various menus and submenus. The submenus
contain the individual configuration items
and parameters. Annex A contains an over-
view of all possible settings that can be
made. The Configuration Manual
u KH 6495-2 contains detailed descriptions
on individual configuration items as well as
other helpful information.
EB 6495-2 EN
Start-up and configuration
Tip
Settings at the controller can also be
performed on a computer using the TROVIS-
VIEW software:
Each menu of the configuration menu has its
own folder in TROVIS-VIEW, which contain
further folders with submenus. In these fold-
ers, configuration items and parameters are
listed.
The controller must be connected to the
software for configuration with TROVIS-
VIEW (see the 'Operation' section). Refer to
u EB 6661 for instructions on how to
operate TROVIS-VIEW.
At the controller, use the cursor keys ( ,
to browse through the configuration menu.
Press the enter key
Press the escape key
Note
Both the keys on the left and right in the key
panel can be used for the configuration
menu.
We recommend to follow the following con-
figuration sequence to configure the control-
ler:
1. Set the control mode, e.g. M.1-1.
2. Set the input, e.g. I.1.1-6.
3. Assign input to controlled variable, e.g.
C.1.1.1-1.
4. Change the set point, e.g. C.2.1.1.
to select a menu item.
to return.
)
7-1