Annex A (configuration guide)
O.2
Analog output AO2
O.2.3
Operating direction <O.2.1≠0>
-1 Increasing
-2 Decreasing
AO2.P1
Y value for AO2=AO2.MIN <O.2.3-1>
Y value for AO2=AO2.MAX <O.2.3-2>
The default value of AO2.P1 is the same as AO2.MIN.
If AO2.MIN is changed, AO2.P1 is set to AO2.MIN.
AO2.P2
Y value for AO2=AO2.MAX <O.2.3-1>
Y value for AO2=AO2.MIN <O.2.3-2>
The default value of AO2.P2 is the same as AO2.MIN.
If AO2.MAX is changed, AO2.P2 is set to AO2.MAX.
O.2.4
Output ramp <O.2.1≠0, O.2.5-0>
-0 Off
-1 Start with DI1
-2 Start with DI2
-3 Start with DI3
-4 Start with DI4
AO2.GD
Gradient <O.2.4≠0>
AO2.TB
Time base <O.2.4≠0>
AO2.ST
Initial value <O.2.4≠0>
O.2.5
Limit output rate <O.2.1≠0, O.2.4-0>
-0 Off
-1 Increasing, continuously active
-2 Decreasing, continuously active
-3 Increasing and decreasing
-4 Increasing. Start with DI1
-5 Increasing. Start with DI2
-6 Increasing. Start with DI3
-7 Increasing. Start with DI4
-8 Decreasing. Start with DI1
-9 Decreasing. Start with DI2
-10 Decreasing. Start with DI3
-11 Decreasing. Start with DI4
AO2.GD1 Gradient for increasing output signal
<O.2.5-1/-3/-4/-5/-6/-7>
AO2.GD2 Gradient for decreasing output signal
<O.2.5-2/-3/-8/-9/-10/-11>
AO2.TB2
Time base <O.2.5≠0>
16-50
[–10.0 ... 110.0 %]
[–10.0 ... 110.0 %] 100.0 %
[0.1 ... 100.0 %]
[s, min, h]
[–10.0 ... 110.0 %]
[0.1 ... 100.0 %]
[0.1 ... 100.0 %]
[s, min, h]
Default
Setting
setting
O.2.3-1
0.0 %
O.2.4-0
1.0 %
s
0.0 %
O.2.5-0
1.0 %
1.0 %
s
EB 6495-2 EN