Operation
6.3 Increase/decrease set
point
Necessary configuration (see section 10.2)
− A1.1 = 2 And A1.5 = 0 or
− A1.1 = 2 and A1.5 = 1 or
− A1.1 = 2 and A1.5 = 2 or
− A1.1 = 2 and A1.5 = 3 or
− A1.1 = 2 and A1.5 = 4
Note
The setting A1.5 = 1, 2, 3 or 4 allows the
operating function to be controlled by the
digital input and over the [I]/[O] keys (auto-
matic level, 'Au' reading in the display).
Changing to the function level ('F u' reading)
is performed only using the [I]/[O] keys.
Press the [I] or [O] key once to change from
the automatic to the function level. To change
from the function to the automatic level, keep
the [O] key pressed for three seconds.
Control to set point
Control to set point.

Increase/decrease set point

Start set point increase/decrease.
Note
The set point increase/decrease is set in the
C1.SP.DIF parameter in TROVIS-VIEW. See
section 10.2.
32
6.4 Selecting the external/in-
ternal set point
Necessary configuration (see section 10.2)
− A1.1 = 3 And A1.5 = 0 or
− A1.1 = 3 and A1.5 = 1 or
− A1.1 = 3 and A1.5 = 2 or
− A1.1 = 3 and A1.5 = 3 or
− A1.1 = 3 and A1.5 = 4
Note
The setting A1.5 = 1, 2, 3 or 4 allows the
operating function to be controlled by the
digital input and over the [I]/[O] keys (auto-
matic level, 'Au' reading in the display).
Changing to the function level ('F u' reading)
is performed only using the [I]/[O] keys.
Press the [I] or [O] key once to change from
the automatic to the function level. To change
from the function to the automatic level, keep
the [O] key pressed for three seconds.
Activate external set point.
Activate internal set point.
EB 5724-8 EN