Switching Over Internal/External Set Point - Samson TROVIS 6495 Series Mounting And Operating Instructions

Industrial controller
Table of Contents

Advertisement

8.3
Switching over
internal/external set point
If the external set point SPE (C.2.1.2-1) is
configured, the set point SP is equal to SPE.
The switchover to an internal set point SPI is
performed in the operating menu.
The controller is in the operating level:
4
Enter the operating menu (see section
8.1).
Switchover to the internal set point SPI
1x Select the menu item Set point.
1x Activate the menu item Set point.
The current set point is displayed:
SP = SPE
1x Activate the set point SP.
The current set point is high-
lighted: SPE
1x Select internal set point SPI.
1x Confirm the setting
SPI is now the active set point.
Note: Determining and changing the inter-
nal set point is described in Section 8.4.
Cascade control
For cascade control (M.1-3) the cascade
can also be opened and closed by switching
over the set point.
The cascade is opened if the following ap-
plies in the slave controller [2]: SP = SPI
The cascade is closed if the following ap-
plies in the slave controller [2]: SP = SPM
8.4
Switching over between
internal set points and
changing them
In the operating menu, one of the set points
SP1, SP2, SP3 or SP4 can be assigned to
the internal set points SPI, depending on the
configuration.
Operating menu
25
EB 6495-2 EN

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Trovis 6495-2

Table of Contents