C.3.1
Control response
Con-
troller
C.3.1.10 Operating point 2 with DI
[1] [2]
-0 Off
[1] [2]
-1 With digital input DI1
[1] [2]
-2 With digital input DI2
[1] [2]
-3 With digital input DI3
[1] [2]
-4 With digital input DI4
[1] [2] Y0.2
Operating point 2
<C3.1.10≠0>
C.3.1.11 Internally controlled output limitation <M.1-4>
[1]
-1 Minimum selection
[1]
-2 Maximum selection
[1]
OC.K1
Limiting band master control-
ler
[1]
OC.K2
Limiting band override control-
ler
C.3.2
Feedforward control
Con-
troller
C.3.2.1
Link input variable SPE
[1] [2]
-0 Off
[1] [2]
-1 To input variable PV
[1] [2]
-2 To inputs DV, TR
M.1-2/-6 Controller [1]: To input TR
C.3.2.2
Valuate input variable SPE <C.3.2.1≠0>
[1] [2]
-1 Result pos./neg.
[1] [2]
-2 Result>= 0
[1] [2]
-3 Result <= 0
[1] [2] K3
Constant, formula:
SPE*K3+K4
[1] [2] K4
Constant, formula:
SPE*K3+K4
C.3.2.3
Link input variables DV, TR
M.1-2/-6 Controller [1]: Link input variable TR
[1] [2]
-0 Off
[1] [2]
-1 To input variable PV
[1] [2]
-2 To set point SP
[1] [2]
-3 To output YPID
[1] [2]
-5 To input variable DV <M.1-2/-6>
EB 6495-2 EN
Annex A (configuration guide)
[–110.0 ... 110.0 %]
[0.1 ... 110.0 %]
[0.1 ... 110.0 %]
[–100.00 ... 100.00]
[–9999.0 ... 9999.0]
Default
Setting
setting
[1]
[2]
C.3.1.10-0
0.0 %
C.3.1.11-1
5.0 %
5.0 %
Default
Setting
setting
[1]
[2]
C3.2.1-0
C.3.2.2-1
1.00
0.0
C.3.2.3-0
16-29