Samson TROVIS 6495-2 Mounting And Operating Instructions page 143

Industrial controller
Hide thumbs Also See for TROVIS 6495-2:
Table of Contents

Advertisement

C.3.3
Additional control functions
Con-
troller
C.3.3.3
Output tracking <C.1.4.1-1/-2/-3/-4>
M.1-1/-2/-3/-5/-6; M.1-4: Controller [1] only
[1] [2]
-0 Off
[1] [2]
-1 With input TR, DI1
[1] [2]
-2 With input TR, DI2
[1] [2]
-3 With input TR, DI3
[1] [2]
-4 With input TR, DI4
C.3.3.6
Increase/decrease actual value with DI
[1] [2]
-0 Off
[1] [2]
-1 With digital input DI1
[1] [2]
-2 With digital input DI2
[1] [2]
-3 With digital input DI3
[1] [2]
-4 With digital input DI4
[1] [2] K9
Constant to increase/decrease
actual value
C.3.3.7
Limit output in manual mode
M.1-3/-4: Controller [1] only
[1] [2]
-0 Off
[1] [2]
-1 On
C.3.3.8
Limit master controller output YM
<M.1-3>
[2]
-0 Off
[2]
-1 Min/Max value = constant
[2]
-2 Minimum value = f(SP0)
[2]
-3 Maximum value = f(SP0)
[2]
-4 Min/Max value = f(SP0)
[2]
YM.MIN Minimum value output master
controller <C.3.3.8≠0>
[2]
YM.MAX Maximum value output master
controller <C.3.3.8≠0>
[2]
YM.K1 Constant minimum value =
SP – YM.K1 <C.3.3.8-2/-4>
[2]
YM.K2 Constant maximum value =
SP + YM.K2 <C.3.3.8-3/-4>
EB 6495-2 EN
Annex A (configuration guide)
[–999.0 ... 9999.0]
[–10.0 ... 110.0 %]
[–10.0 ... 110.0 %]
[0.0 ... 100.0 %]
[0.0 ... 100.0 %]
Default
Setting
setting
[1]
[2]
C.3.3.3-0
C.3.3.6-0
0.0
C.3.3.7-1
C.3.3.8-0
0.0 %
100.0 %
100.0 %
100.0 %
16-33

Advertisement

Table of Contents
loading

Table of Contents