Samson TROVIS 6495-2 Mounting And Operating Instructions page 134

Industrial controller
Hide thumbs Also See for TROVIS 6495-2:
Table of Contents

Advertisement

Annex A (configuration guide)
C.2.3
Set point ramp function
Con-
troller
C.2.3.1
Set point ramp
[1] [2]
-0 Off
[1] [2]
-1 Start with DI1, SP=PV
[1] [2]
-2 Start with DI2, SP=PV
[1] [2]
-3 Start with DI3, SP=PV
[1] [2]
-4 Start with DI4, SP=PV
[1] [2]
-5 Start with DI1, SP=SP.ST
[1] [2]
-6 Start with DI2, SP=SP.ST
[1] [2]
-7 Start with DI3, SP=SP.ST
[1] [2]
-8 Start with DI4, SP=SP.ST
[1] [2]
-9 Continuously active
[1] [2] SP.GD
Gradient <C.2.3.1≠0>
[1] [2] SP.TB
Time base <C.2.3.1≠0>
[1] [2] SP.ST
Initial set point
<C.2.3.1-5/-6/-7/-8>
[1] [2] SP.RH
Hold set point ramp at devia-
tion band <C.2.3.1≠0>
Firmware version 1.11 and lower:
C.2.3.2
Hold set point ramp with DI <C.2.3.1≠0>
[1] [2]
-0 Off
[1] [2]
-1 With digital input DI1
[1] [2]
-2 With digital input DI2
[1] [2]
-3 With digital input DI3
[1] [2]
-4 With digital input DI4
C.2.4
Additional set point functions
Con-
troller
C.2.4.1
Valuate external set point SPE <C.2.1.2≠0>
[1] [2]
-0 Off
[1] [2]
-1 On
[1] [2] K1
Valuation: SPE' = SPE*K1+K2
<C.2.4.1-1>
[1] [2] K2
Valuation: SPE' = SPE*K1+K2
<C.2.4.1-1>
16-24
[0.0 ... 9999.0]
[s, min, h]
[–999.0 ... 9999.0]
[0.1 ... 1000.0 %] 1000.0 %
[0.1 ... 100.0 %]
[–100.00 ... 100.00]
[–9999.0 ... 9999.0]
Default
Setting
setting
[1]
[2]
C.2.3.1-0
1.0
s
0.0
100.0 %
C.2.3.2-0
Default
Setting
setting
[1]
[2]
C.2.3.2-0
1.00
0.0
EB 6495-2 EN