Analog input AI4
I.4.6
Manual mode Controller [1] upon signal failure <I.4.5≠0>
-0 Off
-1 Constant output value at AO1
-2 Constant output value at AO2
-3 Constant output value at AO3
-4 Constant output value at AO1
-5 Constant output value at SO2
-6 With last output value
AO1.K1
Constant output value at AO1 <I.4.6-1>
AO2.K1
Constant output value at AO2 <I.4.6-2>
AO3.K1
Constant output value at AO3 <I.4.6-3>
SO1.K1
Constant output value at SO1 <I.4.6-4>
SO2.K1
Constant output value at SO2 <I.4.6-5>
I.4.7
Manual mode Controller [2] upon signal failure
-0 Off
-1 Constant output value at AO1
-2 Constant output value at AO2
-3 Constant output value at AO3
-4 Constant output value at AO1
-5 Constant output value at SO2
-6 With last output value
AO1.K1
Constant output value at AO1 <I.4.7-1>
AO2.K1
Constant output value at AO2 <I.4.7-2>
AO3.K1
Constant output value at AO3 <I.4.7-3>
SO1.K1
Constant output value at SO1 <I.4.7-4>
SO2.K1
Constant output value at SO2 <I.4.7-5>
I.5
Digital input DI1
I.5.1
Invert
-0 Off
-1 On
EB 6495-2 EN
Annex A (configuration guide)
<O.1.1-1>
<O.2.1-1>
<O.3.1-1>
<O.4.1-1>
<O.5.1-1>
<O.1.1-1/O.2.1-1/O.3.1-1/
O.4.1-1/O.5.1-1>
[–10.0 ... 110.0 %]
[–10.0 ... 110.0 %]
[–10.0 ... 110.0 %]
[–10.0 ... 110.0 %]
[–10.0 ... 110.0 %]
<M.1-5/-6, I.4.5≠0>
<O.1.1-2>
<O.2.1-2>
<O.3.1-2>
<O.4.1-2>
<O.5.1-2>
<O.1.1-2/O.2.1-2/O.3.1-2/
O.4.1-2/O.5.1-2>
[–10.0 ... 110.0 %]
[–10.0 ... 110.0 %]
[–10.0 ... 110.0 %]
[–10.0 ... 110.0 %]
[–10.0 ... 110.0 %]
Default
Setting
setting
I.4.6-0
0.0 %
0.0 %
0.0 %
0.0 %
0.0 %
I.4.7-0
0.0 %
0.0 %
0.0 %
0.0 %
0.0 %
Default
Setting
setting
I.5.1-0
16-11