Samson TROVIS 6495-2 Mounting And Operating Instructions page 27

Industrial controller
Hide thumbs Also See for TROVIS 6495-2:
Table of Contents

Advertisement

4 digital inputs
Outputs
3 analog outputs
7 digital outputs
Relays
Transistor
outputs
Interfaces
Infrared
interface
EB 6495-2 EN
Actuation
Nominal signal range
Max. permissible signal
range
Load
Error of outputs
Ambient temperature in-
fluence
Resolution
Static destruction limit
4 relays with floating closing contact (NO), can be inverted
Permissible contact load
Spark suppression
External supply
Transmission protocol
Data that can be trans-
mitted
Transmission rate
Angle of reflected beam
Distance between infra-
red adapter and con-
troller
Design and principle of operation
Floating switching contact or external switching
voltage 24 V DC, 3 mA; sets of two digital inputs
are galvanically connected on one side
Signal state OFF: 0 to 10 V
Signal state ON: 17 to 31 V
Signal inversion adjustable
0 to 20 mA, 4 to 20 mA, 0 to 10 V, 2 to 10 V
0 (2.4) to 22 mA or 0 (1.2) to 11 V
<750 Ω for current; >3 kΩ for voltage
<±0.2 % of nominal signal range for zero, span,
linearity
<±0.1 %/10 K for zero and span (based on 20 °C)
<0.03 %, relating to nominal signal range
±30 V
264 V AC, 1 A AC, cos ϕ = 1 or 250 V DC,
0.1 A DC
Connected in series C = 2.2 nF and varistor
300 V AC, in parallel to each relay contact
3 electrically isolated transistor outputs
3 to 42 V DC, max. 30 mA
SAMSON-specific protocol (SSP)
Controller settings, process variables, operating
status
9600 bit/s
50°
≤70 cm
3-13