Samson TROVIS 6495-2 Mounting And Operating Instructions page 156

Industrial controller
Hide thumbs Also See for TROVIS 6495-2:
Table of Contents

Advertisement

Annex A (configuration guide)
O.1
Analog output AO1
-36 [2] Abs. error signal |e| <M.1-3/-4/-5/-6>
-37 Output master controller YM <M.1-3>
-38 Y1*Y2*AO1.KM/100 <M.1-5/-6>
-39 (100–Y1)*Y2*AO1.KM/100 <M.1-5/-6>
AO1.FX
Constant output value <O.1.1-4>
A01.KM
Constant, mixing operation <O.1.1-38/-
39>
O.1.2
Output signal <O.1.1≠0>
-1 4-20 mA
-2 0-20 mA
-3 0-10 V
-4 2-10 V
AO1.MIN
Minimum output value
AO1.MAX Maximum output value
O.1.3
Operating direction <O.1.1≠0>
-1 Increasing
-2 Decreasing
AO1.P1
Y value for AO1=AO1.MIN <O.1.3-1>
Y value for AO1=AO1.MAX <O.1.3-2>
The default value of AO1.P1 is the same as AO1.MIN.
If AO1.MIN is changed, AO1.P1 is set to AO1.MIN.
AO1.P2
Y value for AO1=AO1.MAX <O.1.3-1>
Y value for AO1=AO1.MIN <O.1.3-2>
The default value of AO1.P2 is the same as AO1.MAX.
If AO1.MAX is changed, AO1.P2 is set to AO1.MAX.
O.1.4
Output ramp <O.1.1≠0, O.1.5-0>
-0 Off
-1 Start with DI1
-2 Start with DI2
-3 Start with DI3
-4 Start with DI4
AO1.GD
Gradient <O.1.4≠0>
AO1.TB
Time base <O.1.4≠0>
AO1.ST
Initial value <O.1.4≠0>
16-46
[–10.0 ... 110.0 %]
[0.0 ... 100.0]
[–10.0 ... 110.0 %]
[–10.0 ... 110.0 %] 100.0 %
[–10.0 ... 110.0 %]
[–10.0 ... 110.0 %] 100.0 %
[0.1 ... 100.0 %]
[s, min, h]
[–10.0 ... 110.0 %]
Default
Setting
setting
0.0 %
1.0
O.1.2-1
0.0 %
O.1.3-1
0.0 %
O.1.4-1
1.0 %
s
0.0 %
EB 6495-2 EN

Advertisement

Table of Contents
loading

Table of Contents