Diagnostics information
F:
Fault cause
R:
System response
A:
Remedy
F:
Mode 0: Slave attempts to write into an incorrect address
22
R:
Restricted telegram data transfer functions
A:
Select own slave address
23
F:
Logical configuring error: Slave-to-slave communications was configured as duplex
operation, however, only one direction is possible for each slave (send or receive)
R:
Send and receive the same data
A:
Either configure send or receive for slave-to-slave communications
F:
Physical data transfer faulted on the SIMOLINK ring
30
R:
No telegram data transfer
A:
Increase send power (launch power) at one of the subsections, replace medium or
connector
31
F:
CRC error (check sum error), data transfer along the ring faulted
R:
Telegram failure
A:
Increase send power (launch power) at one of the subsections, replace medium or
connector
32
F:
Timeout error in the SIMOLINK ring, bus node signals a fault
R:
No telegram data transfer
A:
FB @SL, evaluates output NDM, beforehand, check node and medium
F:
Mode 0: Signaled SIMOLINK cycle time (in the special telegram from SL master)
33
does not correspond to the configured equivalent sampling time
R:
Restricted telegram data transfer functions
A:
In the HW Config: Adapt the equivalent sampling time of the slave to that of the SL
master
Table 4-9
Error output, SIMOLINK-FBs

4.4.6 Options and accessories

The following are available to configure a SIMOLINK coupling and as
spare part:
Table 4-10
Application Module FM 458 - User Manual
6DD1904-0AE0
Edition 12.2001
Order No.
Components
6SE7090-0XX84-0FJ0
SLB module, spare part
(without documentation, without connector)
6SX7010-0FJ00
SLB module, retrofit package
(documentation, 2 fiber-optic cable connectors, 5m
plastic opto-cable, 1 connector for terminal X470)
6SY7000-0AD15
Attachment for SLB
(2 LWL cables, 5m plastic opto-cable)
6SX7010-0FJ50
System package for SLB
(40 fiber-optic cable connectors, 100m plastic opto-
cable, 20 connectors for terminal X470)
SIMOLINK option modules and accessories