Technical Data - Siemens SIMADYN D FM 458 User Manual

Application module
Table of Contents

Advertisement

Product description

2.3.6 Technical data

Order No.
Analog outputs
2-28
/O expansion module EXM 438-1
Number
Version
Electrical isolation
Output voltage range
Output current
Resolution
Conversion time per channel, typ.
Accuracy
Integral linearity error, max.
Gain error, max.
Offset error, max.
Slew rate
Voltage output
Short-circuit protection
Short-circuit current
Number
Version
Electrical isolation
Output voltage range
Output current
Resolution
Conversion time per channel, typ.
Accuracy
Integral linearity error, max.
Gain error, max.
Offset error, max.
Slew rate
Voltage output
Short-circuit protection
Short-circuit current
6DD1607 0CA1
4
No
- 10 V to + 10 V
± 10 mA
12 bit
4 µs
± 1 LSB
± 0,3 %
± 24 mV
approx. 3,5 V/µs
Yes (with respect to ground)
approx. 100 mA
4
No
- 10 V to + 10 V
± 10 mA
16 bit
2 µs
± 1 LSB
± 0,1 %
± 1 mV
approx. 0,7 V/µs
Yes (with respect to ground)
approx. 27 mA for a chanel