Status Displays; Technical Data - Siemens SIMADYN D FM 458 User Manual

Application module
Table of Contents

Advertisement

Product description

2.4.6 Status displays

There are two LED displays provided under the upper housing cover of
the FM 448 communications expansion module. These provide
information about the actual operating status.
Table 2-21
The green and yellow LEDs are only visible from the top through the
NOTE
cooling slots of the housing.

2.4.7 Technical data

Order No.
Voltage, currents
Dimensions
2-36
LED
Status
green
dark
PROFIBUS not initialized
flashing
fatal error:
5 Hz
The error code can be read at function block @CSPRO
and then contact the SIMADYN D Hotline
The connection to the associated CPU module is being
flashing
initialized (@CSPRO): Check the configuring
1 Hz
bright
Initialization O.K.
yellow
dark
No bus operation (initialization phase)
flashing
Bus error/fault, e.g. short-circuit:
5 Hz
Check the bus cable and other nodes
flashing
COM database not available or inactive when downloading
(only for PROFIBUS)
1 Hz
flashing
CFC- and COM configuring do not match:
0.5 Hz
Restricted bus operation possible (only for PROFIBUS)
bright
Bus operation O.K.
Status displays of the communications expansion module FM 448
Communications expansion module
EXM 448
Rated voltage
Typical, current drain
Assignment, slots
Dimensions W x H x D [mm]
Weight
Diagnostics information
6DD1607-0EA0
+5 V
0,3 A
1
25 x 290 x 210
0,85 kg
Application Module FM 458 - User Manual
6DD1904-0AE0
Edition 12.2001

Advertisement

Table of Contents
loading

Table of Contents