The following errors can occur and are displayed at the ERROR output:
Error code
Explanation
0xB210
OK
0xB211
Logical module address invalid
0xB212
Data set number not valid
0xB213
Invalid table data format
0xB214
The data format of the new data set
does not match that of the previously
transferred data set
0xB215
FM 458 does not respond
0xB216
Table is too large
0xB217
Table is not complete (X / Y values)
0xB218
REQTAB is reset during processing
0xB219
REQDB reset during processing
0xB21A
DB number is not valid
0xB21B
TIMEOUT when receiving the
acknowledge telegram
0xB21C
Invalid processing status
Errors associated with the SFC58 or SFC59 are displayed at the ERROR
output.
Application Module FM 458 - User Manual
6DD1904-0AE0
Edition 12.2001
Remedy
-
Specify a valid module address at input
LADDR.
Enter the tabular values in an increasing
sequence in the DB.
Tabular values must have data type REAL for
the TAB and data type DINT for the TAB_D.
Ensure that all of the tabular values have the
same data format.
Check the communications connection and
configuring.
Transfer the table in sub-sets, i.e. either
distribute tabular values over several DBs or
after each partial transfer write new
(additional) tabular values into DB and
transfer.
Complete the table, there must be a Y value
for each X value.
Transfer the tabular values again.
Transfer the tabular values again.
Specify a valid DB number.
Check the communications coupling and
configuring. Transfer the tabular values again
Check the configuring of the WR_TAB.
Configuring
4-37