Configuring
Value
Diagnostics information
F:
Fault cause
R:
System response
A:
Remedy
F:
Memory access problem (internal error message)
5
R:
No telegram data transfer
A:
Reduce the size of the application software or move to another process module
6
F:
Send/receive block(s) signal: Central block @SL not configured
R:
No telegram data transfer
A:
Insert @SL in the software (min. 4 x sampling time of send/receive blocks)
9
F:
This software does not support this hardware combination, e.g. CS8+SLB module
R:
No telegram data transfer
A:
Use an EXM 448-1 or ITSL module for the drive coupling
F:
Modes 0, 2 and 4: Block was not configured in an interrupt task
10
R:
No telegram data transfer
A:
Configure the appropriate block in the interrupt task
11
F:
Modes 1 and 3: Block was not configured in a cyclic task
R:
No telegram data transfer
A:
Configure the appropriate block in a cycle task
12
F:
Mode 5: Block was not configured in a cyclic task with T1=T0
R:
No telegram data transfer
A:
In HW Config: Select T1=T0, configure the appropriate block in cyclic task T1
F:
Mode 4: Equivalent sampling time is not equal to T0
13
R:
No telegram data transfer
A:
In HW Config: Select an equivalent sampling time = T0
14
F:
Modes 0, 2 and 4: Interrupt source for the interrupt task is incorrect
R:
No telegram data transfer
A:
In HW Config: Set the interrupt task source as in the assignment table
15
F:
Mode 1: Not all send/receive blocks in one sampling time
R:
No telegram data transfer
A:
Configure all of the send/receive blocks in the same sampling time
F:
Incorrect mode setting
16
R:
No telegram data transfer
A:
Set a valid mode (mode 0...5) at FB @SL
17
F:
Mode 0, FB @SL: incorrect node address (slave) at input ASL
R:
No telegram data transfer
A:
Select a valid setting at input ASL: 1...200
18
F:
FB @SL signals: No send and receive blocks available
R:
No telegram data transfer
A:
Configure send and/or receive block(s)
F:
No. of SIMOLINK telegrams too high or SIMOLINK cycle time exceeded
19
R:
Telegram data transfer up to max. possible number
A:
Configure max. 1021 net telegrams or increase SIMOLINK cycle time or
configure fewer SIMOLINK blocks (refer to the formula)
20
F:
Send/receive block signals: Incorrect slave address
R:
Restricted telegram data transfer functions
A:
Select valid slave address: 0...200
F:
Send/receive block signals: Channel number incorrect
21
R:
Restricted telegram data transfer functions
A:
Select a valid channel number: 0...7
4-30
Application Module FM 458 - User Manual
6DD1904-0AE0
Edition 12.2001