I/O Memory Allocation
Address
Words
Bits
A527
A52700
to
A52707
A52709
A528
A52800
to
A52807
A52808
to
A52815
A598
A59800
AUDIN - 8, avenue de la malle - 51370 Saint Brice Courcelles - Tel : 03.26.04.20.21 - Fax : 03.26.04.28.20 - Web : http: www.audin.fr - Email : info@audin.fr
Name
Online Ed-
The Online Editing Disable Bit
iting Dis-
(A52709) is valid only when this
able Bit
byte contains 5A.
Validator
To disable online editing from a
Programming Device, set this
byte to 5A and turn ON A52709.
(Online editing refers to changing
or adding to the program while
the PLC is operating in
MONITOR mode.)
Online Ed-
Turn this bit ON to disable online
iting Dis-
editing. The setting of this bit is
able Bit
valid only when A52700 to
A52707 have been set to 5A.
RS-232C
These flags indicate what kind of
Port Error
error has occurred at the RS-
Flags
232C port; they are automatically
turned OFF when the RS-232C
port is restarted.
(These flags are not valid in pe-
ripheral bus mode and only bit 5
is valid in NT Link mode.)
Bits 0 and 1: Not used.
Bit 2: ON when there was a parity
error.
Bit 3: ON when there was a
framing error.
Bit 4: ON when there was an
overrun error.
Bit 5: ON when there was a
timeout error.
Bits 6 and 7: Not used.
Peripheral
These flags indicate what kind of
Port Error
error has occurred at the periph-
Code
eral port.
FPD
Turn this bit ON to set the moni-
Teaching
toring time automatically with the
Bit
teaching function.
While A59800 is ON, FPD(269)
measures how long it takes for
the diagnostic output to go ON
after the execution condition
goes ON. If the measured time
exceeds the monitoring time, the
measured time is multiplied by
1.5 and that value is stored as
the new monitoring time.
(The teaching function can be
used only when a word address
has been specified for the moni-
toring time operand.)
CS/CJ-series PLC
Function
5A:
A52709
enabled
Other
value:
A52709
disabled
1: Disabled
0: Not dis-
abled
See Func-
tion
column.
1: Teach
monitoring
time
0: Teaching
function off
Section 9-3
CX-Simulator
Settings
Function
Same as
CS/CJ-series
PLC.
Same as
CS/CJ-series
PLC.
Not used.
Not used.
Same as
CS/CJ-series
PLC.
Settings
When
valid, on-
line editing
itself is
disabled.
(Reflected
after a
password
input for
CS/CJ-
series
PLC.)
227