Samson TROVIS 5179 Mounting And Operating Instructions page 58

District heating controller
Table of Contents

Advertisement

Appendix
Thermal disinfection for preventing legionella infection causes
4
high return flow temperatures during the disinfection cycle (return flow temperature limita-
tion suspended),
4
high storage temperatures after thermal disinfection has been concluded,
4
lime scale (possibly), which can have a negative effect on heat exchanger performance.
Note!
This function is not available when a storage tank thermostat is used.
Functions
Storage sensor SF1
Thermal disinfection
58
EB 5179 EN
WE
Configuration
ON
Co4 -> Fb00 = ON
OFF
Co4 -> Fb08 = ON
3
Day of the week / 1–7, 1, 2, ..., 7 with
1–7 = every day, 1 = Monday, ..., 7 = Sunday
70 °C
Disinfection temperature / 60 to 90 °C
5 °C
Charging boost / 0 to 30 °C
00:00
Start time / 00:00h to 23:30h (in steps of 30 minutes)
04:00
Stop time / 00:00h to 23:30h (in steps of 30 minutes)