Parameter List - Samson TROVIS 5179 Mounting And Operating Instructions

District heating controller
Table of Contents

Advertisement

12.2 Parameter list

PA1 to PA3: Heating circuits HK1 to HK3
Display
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Parameter designation
Range of values (default settings)
Gradient of the heating characteristic, flow
0.4 to 3.2 (1.8)
Level of the heating characteristic, flow
–30 to 30 °C (0 °C)
4-point characteristic
Press key to adjust the following parameters:
outdoor temperature,
flow temperature,
return flow temperature and
set-back difference.
4-point characteristic
Point 1: Outdoor temperature
Outdoor temperatures of the points 2, 3, 4 are marked by squares
below the numbers 2, 3, 4.
–30 to 90 °C
(point 1 = –15 °C, point 2 = –5 °C, point 3 = 5 °C, point 4 = 15 °C)