Heating and district heating controller (32 pages)
Summary of Contents for Samson TROVIS 5179
Page 1
Automation System TROVIS 5100 District Heating Controller TROVIS 5179 Mounting and Operating Instructions EB 5179 EN Firmware version 1.2x ® Edition August 2005 Electronics from SAMSON...
Page 2
Moreover, we do not guarantee that the buyer can use the product for an intended purpose. SAMSON rejects any liability for claims by the buyer, especially claims for compensation including lost profits or any other financial loss, except the damage was caused intentionally or by gross negligence.
Operation Operation The controller is ready for use with the temperatures and operating schedules preset by the manufacturer. On start-up, the current time and date need to be set at the controller (–> section 1.5). 1.1 Operating elements The operating controls are located in the front panel of the controller and protected by a Plexi- glas door.
Operation 1.1.2 Operating switches Heating circuit mode selector switch Automatic mode with switchover between rated operation and reduced operation Rated operation Reduced operation Manual operation: Control valve opens - stationary - closes (for on/off control: + ON, 0 OFF) DHW circuit mode selector switch The operating mode icon stickers are included in the scope of delivery and can be stuck on the front above the mode selector switch for control circuit 2 (middle), if required.
Operation The assignment of the control circuits to the mode selector switches depends on the system code number (Anl): Mode selector switch System (Anl) Middle Bottom Heating circuit 1 Heating circuit 2 Pre-control circuit Heating circuit 1 DHW heating Heating circuit 2 Heating circuit 1 Heating circuit 2 Heating circuit 3/Pre-control...
Operation 1.3 Display During operation, the display indicates the current time as well as information about the opera- tion of the controller. The times-of-use are represented by black squares below the row of num- bers at the top of the display. Icons indicate the operating status of the controller. The controller status can be displayed in the operating level (InF level) (–>...
Operation 1.4 Displaying data Measured values, set points, times-of-use, public holidays and vacation periods can be re- trieved and displayed in the InF1 to InF9 information levels. The various displays are listed in section 11.4. InF1: Heating circuit 1 InF2: Heating circuit 2 InF3: Heating circuit 3...
Operation 1.5 Setting the controller time The current time and date need to be set immediately after start-up and after a power failure lasting longer than 24 hours. Proceed as follows: Switch to configuration and parameter level. Display: PA1 Select PA5 parameter level. Open PA5 parameter level.
Page 12
Operation Confirm date. Display: Year. Activate editing mode for the controller year. Change year setting. Confirm year. Exit PA5 parameter level. Return to the operating level. Note! The controller automatically returns to the operating level if the keys are left unpressed for two minutes.
Operation 1.6 Setting the times-of-use Two times-of-use can be set for each day of the week. If just one time-of-use is required, the start and stop times of the second time-of-use must be programmed to identical times. The time schedules for the three heating circuits, DHW heating and the circulation pump can be read over Modbus.
Page 14
Operation Activate editing mode for times-of-use. Display: 1–7 Select period/day for which the times-of-use are to be valid: 1–7 = every day, 1 = Monday, 2 = Tuesday, ..., 7 = Sunday Activate editing mode for period/day. Display shows: START ; blinks Edit start time (steps of 30 minutes).
Operation 1.6.1 Copying the times-of-use The times-of-use of heating circuit 1 (2) can be copied and used for heating circuit 2 (3). Copy function Parameter level Icon HK1 –> HK2 COPY2 HK2 –> HK3 COPY3 Proceed as follows: Switch to configuration and parameter level. Display: PA1 Select parameter level.
Operation 1.6.2 Entering public holidays On public holidays, the times-of-use specified for Sunday apply. A maximum of 20 public holi- days may be entered. Parameters Level / Range of values Public holidays f. heating circuit 1 – PA1 / 01.01 to 31.12 Public holidays f.
Page 17
Operation Note! Public holidays that are not assigned to a specific date should be deleted by the end of the year so that they are not carried on into the following year. Deleting a public holiday: Select the holiday you wish to delete in the datapoint for public holidays. Confirm selection.
Operation 1.6.3 Entering vacation periods During vacation periods, the controller constantly remains in the reduced operating mode. The system is monitored for frost. A maximum of 10 vacation periods can be entered. Parameters Level / Range of values Vacation period for heating circuit 1 –...
Page 19
Operation Return to the operating level. Note! Vacation periods that are not assigned to a specific date should be deleted by the end of the year so that they are not carried on into the following year. Deleting vacation periods: Select the vacation period you wish to delete in the datapoint for vacation periods.
Start-up Start-up 2.1 Setting the system code number 10 different hydraulic schematics are available. Each system configuration is represented by a system code number. The different schematics are dealt with in section 4. Available controller functions are described in sections 5, 6 and 7. Changing the system code number resets previously adjusted function blocks to their default set- tings (WE).
Start-up 2.2 Activating and deactivating functions A function is activated or deactivated in the associated function block. The numbers 0 to 24 in the top row of the display represent the respective function block numbers. When a configura- tion level is opened, the activated function blocks are indicated by a black square on the right-hand side below the function block number.
Page 22
Start-up Confirm settings. If the function block is not closed, further function block parameters can be adjusted. Proceed as follows: Make the desired changes and confirm. If applicable, the next function block parameter is displayed. Confirm all parameters to exit the opened function block. To adjust additional function blocks, repeat the steps in the fields highlighted in gray.
Start-up 2.3 Changing parameters Depending on the set system code number and the activated functions, not all parameters listed in the parameter list in the Appendix (–> section 12.2) might be available. The parameters are grouped by topics: PA1: Heating circuit 1 PA2: Heating circuit 2 PA3: Heating circuit 3 PA4: DHW heating...
Start-up 2.3.1 Enter key number Some functions are protected against unintentional or unauthorized access. These functions can only be activated or deactivated after the valid key number has been entered. The valid key number for initial start-up can be found on page 137. To avoid unauthorized use of the key number, remove the page or make the key number unreadable.
Page 25
Start-up erence temperature) measured directly at the point of measurement. Sensor calibration is to be activated in Co6 via function block Fb23. Proceed as follows: Switch to configuration and parameter level. Display shows: PA1 Select Co6 level. Open Co6 level. Display shows: Fb00 Select function block Fb23.
Start-up Note! The sensor values adjusted are not reset by the Loading default settings function. 2.6 Resetting to default values All parameters and function blocks from any parameter level can be reset to their default set- tings (WE). Proceed as follows: Reset to default settings.
Manual operation Manual operation Switch to manual mode to configure all outputs (see wiring diagram in section 11). Proceed as follows: Position all selector mode switches to +, 0 or –. Select PU pump manual level. Open pump manual level. Select pump PU1 to PU5: PU1: BA11 PU2: BA12...
Systems Systems There are 10 hydraulic schematics. System code number (Anl) Outdoor temperature compensated flow temperature Heating control with variable return flow temperature limitation Number of heating circuits No. of heating circuits w. mixing valve • • • • • •...
Page 29
Systems System Anl 1 RüF1 RüF2 RüF prim Default setting Co1 -> Fb00 = OFF (without RF1) Co1 -> Fb01 = OFF (without RüF1) Co1 -> Fb02 = ON (with AF1) Co2 -> Fb00 = OFF (without RF2) Co2 -> Fb01 = OFF (without RüF2) Co2 ->...
Page 30
Systems System Anl 2 RüF1 RüF2 RüF prim Default setting Co1 -> Fb00 = OFF (without RF1) Co1 -> Fb01 = OFF (without RüF1) Co1 -> Fb02 = ON (with AF1) Co2 -> Fb00 = OFF (without RF2) Co2 -> Fb01 = OFF (without RüF2) Co2 ->...
Page 31
Systems System Anl 3 RüF1 RüF2 RüF RF2 UP3 prim Default setting Co1 -> Fb00 = OFF (without RF1)* Co1 -> Fb01 = OFF (without RüF1) Co1 -> Fb02 = ON (with AF1) Co2 -> Fb00 = OFF (without RF2)* Co2 ->...
Page 32
Systems System Anl 4 RüFTW RüF1 RüF prim Default setting Co1 -> Fb00 = OFF (without RF1) Co1 -> Fb01 = OFF (without RüF1) Co1 -> Fb02 = ON (with AF1) Co4 -> Fb00 = ON (with SF1) Co4 -> Fb01 = ON (with SF2) Co4 ->...
Page 33
Systems System Anl 5 RüF1 RüFTW RüF prim Default setting Co1 -> Fb00 = OFF (without RF1)* Co1 -> Fb01 = OFF (without RüF1) Co1 -> Fb02 = ON (with AF1) Co4 -> Fb00 = ON (with SF1) Co4 -> Fb01 = ON (with SF2) Co4 ->...
Page 34
Systems System Anl 6 RüF1 RüF2 RüF3 Default setting Co1 -> Fb00 = OFF (without RF1) Co1 -> Fb01 = OFF (without RüF1) Co1 -> Fb02 = ON (with AF1) Co2 -> Fb00 = OFF (without RF2) Co2 -> Fb01 = OFF (without RüF2) Co2 ->...
Page 35
Systems System Anl 7 RüF1 RüF RüFTW prim Default setting Co1 -> Fb00 = OFF (without RF1) Co1 -> Fb01 = OFF (without RüF1) Co1 -> Fb02 = ON (with AF1) Co4 -> Fb00 = ON (with SF1) Co4 -> Fb01 = ON (with SF2) Co4 ->...
Page 36
Systems System Anl 8 RüF1 RüF RüFTW prim Default setting Co1 -> Fb00 = OFF (without RF1) Co1 -> Fb01 = OFF (without RüF1) Co1 -> Fb02 = ON (with AF1) Co4 -> Fb00 = ON (with SF1) Co4 -> Fb01 = ON (with SF2) Co4 ->...
Page 37
Systems System Anl 9 VFsek RüF1 RüF2 RüFTW Default setting Co1 -> Fb00 = OFF (without RF1) Co1 -> Fb01 = OFF (without RüF1) Co1 -> Fb02 = ON (with AF1) Co2 -> Fb00 = OFF (without RF2) Co2 -> Fb01 = OFF (without RüF2) Co2 ->...
Page 38
Systems System Anl 10 RüF1 RüF2 RK RüFTW RüF AF1 AF2 prim Default setting Co1 -> Fb00 = OFF (without RF1) Co1 -> Fb01 = OFF (without RüF1) Co1 -> Fb02 = ON (with AF1) Co2 -> Fb00 = OFF (without RF2) Co2 ->...
Functions of the heating circuit Functions of the heating circuit Which controller functions are available depends on the selected system code number (Anl). 5.1 Functioning principle The heating circuit with the highest flow set point has priority. This principle applies to all heat- ing circuits with mixing valves.
Functions of the heating circuit If just one outdoor sensor should be connected, connect it to AF1. This outdoor temperature is then used also for HK2 and HK3. 5.2.1 Gradient characteristic Basically, the following rule applies: a decrease in the outdoor temperature causes the flow tem- perature to increase.
Page 41
Functions of the heating circuit The Max. flow temperature and Min. flow temperature parameters mark the upper and lower lim- its of the flow temperature. [˚C] P1 to 4 Points 1 to 4 VLmax t VL Flow temperature Outdoor temperature ...min Minimum t VL ...max...
Functions of the heating circuit Note! The 4-point characteristic function can only be activated when the Adaptation function is not active (Co1, 2, 3 -> Fb07 = OFF). 5.3 Fixed set point control During the times-of-use, the flow temperature can be controlled according to a fixed set point. Outside the times-of-use, this set point is reduced by the Set-back difference .
Functions of the heating circuit Configuration Function Differential temperature control using variable Co1, 2, 3 -> Fb18 = ON weighting factors Proportional gain factor K /0.1 to 999 200 s Reset time T / 1 to 999 s 20 °C Intended temp.
Functions of the heating circuit When the outdoor temperature falls below this value (less 0.5 °C hysteresis), heating operation is restarted immediately. With the default settings, this means that, at night, the system is switched off at an outdoor tem- perature of 10 °C to save energy.
Functions of the heating circuit Note! Summer mode only becomes effective when the controller is in automatic mode ( 5.6 Delayed outdoor temperature adaptation The calculated outdoor temperature is used to determine the flow temperature set point. The heat response is delayed when the outdoor temperature either decreases, or increases and de- creases.
Optimization, Adaptation, Flash adaptation or Room tem- perature-dependent control functions have been activated. TROVIS 5179 Type 5244/5257-5 Fig. 4 · Wiring plan for Type 5244/5257-5 Room Sensors/TROVIS 5179 Controller Configuration Function Room sensor RF1, 2, 3 Co1, 2, 3 -> Fb00 = ON 5.9 Optimization with room sensor...
Page 47
Functions of the DHW circuit There are two types of optimization depending on the activation conditions: Outdoor temperature-dependent advance heating, room temperature-dependent deacti- vation The controller activates the heating depending on the outdoor temperature before the time-of-use starts in normal operation. The Advance heating time is based on an outdoor temperature of –12 °C.
Functions of the DHW circuit Parameter level / Range of values Parameters Day set point 20 °C PA1, 2, 3 / 10 to 90 °C Night set point 17 °C PA1, 2, 3 / 10 to 90 °C Sustained temperature 10 °C PA1, 2, 3 / 10 to 90 °C 5.10 Flash adaptation...
Appendix Parameter level / Range of values Parameter Day set point 20 °C PA1, 2, 3 / 10 to 90 °C 5.12 Room temperature-dependent control In systems Anl 6 and 9, the Room temperature-dependent control function can be separately activated for each heating circuit. The Room sensor function must be activated for this function. Flow and return flow sensors only serve to display the temperature and can therefore be deacti- vated.
Appendix Configuration Functions Room sensor RF1, 2, 3 Co1, 2, 3 -> Fb00 = ON Room temperature dependent control Co1, 2, 3 -> Fb06 = ON Parameter optimization Co1, 2, 3 -> Fb16 Flow sensor OFF when room temperature Co1, 2, 3 -> Fb17 dependent control is used 5.13 Pump management To control the circulation pumps for the heating circuits (UP1 and UP2), reed relay outputs can...
Appendix 5.14 Releasing the heating circuit The release of the heating circuit in automatic mode is a default setting after the time schedule has been programmed. In addition, it is possible to release the heating circuit over the corre- sponding potentiometer inputs. When no signal exists at these inputs and the slide switch of the heating circuit is positioned to automatic mode ( ), the heating circuit is in stand-by mode (i.e.
Functions of the DHW circuit Functions of the DHW circuit 6.1 DHW heating in the storage tank charging system Heat exchanger charging pump VFS/VFT Flow sensors Storage tank charging pump Storage sensor 1 Storage sensor 2 Circulation pump Cold water Fig.
Page 53
System-wide functions The Mixing valve always active function allows the heat exchanger to maintain the charging temperature using the mixing valve. The heat exchanger charging pump remains switched on and the return flow temperature is not limited outside the times-of-use. When the flow sensor VFS is active, the set point in the heat exchanger charging circuit is af- fected by the system deviation in the storage tank charging circuit when the storage tank charg- ing pump is switched on:...
Appendix Parameter level / Range of values Parameters DHW demand ON 40 °C PA4 / 20 to 90 °C DHW demand OFF 45 °C PA4 / 20 to 90 °C Charging temperature 55 °C PA4 / 20 to 90 °C Heat exchanger charging pump 50 °C PA4 / 20 to 90 °C...
Page 55
Appendix When there is no heating operation or when the flow temperature in the system is lower, the storage tank charging pump is switched on immediately. If a storage tank thermostat is used, the storage tank charging pump is switched on when the temperature T = Charging temperature –...
Appendix Parameter level / Range of values Parameters DHW demand ON 40 °C PA4 / 20 to 90 °C Hysteresis 5 °C PA4 / 0 to 30 °C Charging temperature 55 °C PA4 / 20 to 90 °C Storage tank charging pump 50 °C PA4 / 20 to 90 °C deactivation limit...
Appendix 6.3.2 Set-back operation In all systems with DHW heating and at least one heating circuit with control valve, DHW heat- ing can be given priority by applying set-back operation. The charging temperature can be monitored with the setting Co4 -> Fb06 = OFF and Activate priority in case of deviation > 0. Configuration Function Reverse control...
Page 58
Appendix Thermal disinfection for preventing legionella infection causes high return flow temperatures during the disinfection cycle (return flow temperature limita- tion suspended), high storage temperatures after thermal disinfection has been concluded, lime scale (possibly), which can have a negative effect on heat exchanger performance. Note! This function is not available when a storage tank thermostat is used.
System-wide functions System-wide functions 7.1 Automatic summer time/winter time changeover The clock is automatically adjusted on the last Sunday in March at 2.00h and on the last Sunday in October at 3.00h. Configuration Function Co5 -> Fb05 = ON Summer time/winter time changeover 7.2 Frost protection The Frost protection function does not work in manual mode.
Page 60
System-wide functions Configuration Function Return flow sensor RüF1, 2, 3 Co1, 2, 3 -> Fb01 = ON Limitation factor / 0 to 25.5 Parameter level / Range of values Parameters Max. return flow temperature 65 °C PA1, 2, 3 / 20 to 90 °C Min.
System-wide functions 7.5 Condensate accumulation control Activate the Condensate accumulation control function to start up condensate accumulation plants, in particular to avoid problematic excess temperatures. The controller response to set point deviations which cause the primary valve to open is attenuated. The controller response to set point deviations which cause the control valve to close remains unaffected.
System-wide functions 7.7 Three-step control The flow temperature can be controlled using a PI algorithm. The valve reacts to pulses that the controller emits when a system deviation occurs. The length of the first pulse, in particular, de- pends on the extent of the system deviation and the selected Proportional gain K (the pulse length increases as K increases).
System-wide functions 7.8 On/off control The flow temperature can be controlled by an on/off signal. The controlled valve is opened when the flow temperature falls below the set point by T = 0.5 x Hysteresis . When the flow tem- perature exceeds the set point by T = 0.5 x Hysteresis , the control valve is closed.
System-wide functions Configuration Functions Continuous-action control for heating circuit Co1, 2, 3 -> Fb14 = ON (gain) / 0.1 to 50.0 200 s (reset time) / 1 to 999 s (derivative-action time) / 0 to 999 s Continuous-action control for DHW heating Co4 ->...
Page 65
System-wide functions A heat meter with pulse output connected at input V (terminal 30) can be used either to limit the system flow rate (parameter code: U) or the system capacity (parameter code: P). The pulse weighting of the heat meter (WMZ) and the type of limitation selected must be entered. The dis- played value corresponds to the unit l/pulse or kWh/pulse.
System-wide functions Settings for flow rate limitation Functions Configuration Limitation of heat meter (WMZ) Co5 -> Fb08 = OFF Pulse input for flow rate or capacity limitation Co5 -> Fb09 = ON, select: U CONST: Limitation constant 4-Pt: Limitation acc. to 4-point characteristic Pulse weighting / 0.1 to 10 Parameter level / Range of values...
Operational faults Operational faults icon blinking on the display. Error immediately Malfunctions or faults are indicated by the appears on the display. Press the enter key to open the error level. It may be possible to view several error alarms by pressing the enter key. As long as an error alarm is present, the error level appears in the display loop, even though it has not been opened by pressing the enter key.
7403b = TROVIS 5174 Controller, sensor breakage bit 03 7919b = TROVIS 5179 Controller, sensor breakage bit 19 The relationship between the set bit and the associated sensor can be found in the Mounting and Operating Instructions (EB) of the recognized LON controller.
Operational faults 8.3 Temperature monitoring The flow temperature and the room temperature can be monitored for any deviations. This func- tion is activated in Co5 -> Fb20. The controller issues an alarm when: the flow temperature deviates from its set point by more than 10 °C for more than 30 minutes the room temperature falls below its set point by 2 °C for more than 30 minutes the return flow temperature limitation is active for more than 30 minutes.
Operational faults 8.4 Monitoring the input terminals for limit violations The controller provides the option to apply limits (in % of measuring range) to two selected in- puts (temperature sensor or analog inputs) and to issue an alert to a higher-level control system by writing in the error status register.
Operational faults 8.5 Error status register The HR 60 and HR 61 error status registers (holding register - 16-bit) are used to indicate con- troller or system errors. HR 60 contains general alarms, whereas special faults are entered in HR 61. In modem mode (Co9 -> Fb01 = ON), the change in state of HR 60 or HR 61 causes the controller to dial the control system.
Operational faults Example of a transfer to the control system: The error status register is transferred as a word <w> in a holding register (HR) whose value is calculated as follows: <w> = ([D0] x <1> + [D1] x <2> ) +...+ ([D11] x <2048>) Holding register 61 (A set bit is indicated by on the right of number): Number = Bit no.
Operational faults 8.6.1 Sending text message in case of a fault alarm Currently, text messages can only be sent to the German D1 network. The corresponding access numbers into the D1 network as well as the mobile phone number of the recipient must be set in the PA9 level: D1 access number: 0171 252 10 02 (add 0 in front when dialing from a private branch exchange)
Page 75
Operational faults Station ID: Digits 0 to 9, P = pause, - = end, max. 14 characters Functions Configuration Modbus Co9 -> Fb00 = OFF Modem Co9 -> Fb01 = OFF Alarm sent as text message Co9 -> Fb06 = OFF Alarm sent per fax Co9 ->...
Communication Communication Using the serial system bus interface, the TROVIS 5179 District Heating Controller can commu- nicate with a building control system. In combination with a suitable software for process visual- ization and communication, a complete control system can be implemented.
Communication GND TD DTR Fig. 8 · Pin assignment of RJ-12 system bus interface 9.1 RS-232-C system bus interface The system bus connection is located at the back of the controller housing (RJ-12 jack). In this case, the controller can be connected either directly to the serial interface of a PC (point-to-point connection) or to a (dial-up) modem.
Communication Configuration Functions Modem Co9 -> Fb01 = ON Modem dialing procedure Co9 -> Fb02 Lock dial-up Co9 -> Fb03 Dial-up also upon corrected fault Co8 -> Fb00 Parameters* Parameter level / Range of values Station address (ST.-NR) PA9 / 1 to 247 (1 to 999 with Co9 ->...
Communication Configuration Functions Modbus Co9 -> Fb00 = ON Modem Co9 -> Fb01 = OFF Modbus 16-bit addressing Co9 -> Fb04 Parameters* Parameter level / Range of values Station address (ST.-NR) PA9 / 1 to 247 (1 to 999 with Co9 -> Fb04 = ON) Baud rate (BAUD) 9600 PA9 / 300 to 19200...
Page 80
Communication Modem timeout (t) When the controller connects to the GLT but without addressing a Modbus data point, the con- nection is closed after the time specified for Modem time-out has elapsed. If the error status reg- ister has not been read during the GLT connection, the controller dials up to the GLT again after the Modem dialing pause (P) has elapsed.
Communication Note! The initialization settings described here are indispensable for operation on a dial-up modem. Nevertheless, it cannot be guaranteed that data are transferred after the initialization settings have been adjusted. Due to the broad range of modems available on the market and the differ- ent commands, refer to the operating manual of the modem for further details.
Communication Flow temperature (b, °C) Return flow temperature (b, °C) Meter identification number (L without enter key, H with enter key) Meter bus address (sent by WMZ) (A, –) Blinking values in combination with black squares in the top row of the display (fault status of the associated meter –>...
Page 83
Communication A system with simultaneous room heating and DHW heating requires maximum energy. A system with a fully charged storage tank which performs only room heating requires less energy. A system which suspends room heating during DHW heating requires less energy. As a result, three different maximum limit values can be specified: Max.
1 to 20 TROVIS 5177 1 to 20 TROVIS 5179 1 to 20 The controller sends its inputs and outputs as well as pulse counters and their pulse duration over the LON network to a TROVIS 5171 Programmable Logic Controller.
Communication 9.6 Requesting/processing an external demand Requesting an external demand The flow temperature set points can be passed on over the LON network in complex heating sys- tems. The external flow set point is compared with the controller’s own flow set point. The higher of the two flow set points is passed on.
Communication Note! In controllers with a firmware version lower than 1.05, the master controller receives the Subnet 1 address and node address 1 and is the decisive controller in LON network terms. It is the only controller that can send alarms over a modem. 9.7 Sending outdoor temperatures and controller time Two outdoor temperatures and the controller time can be sent over the LON bus which are taken on by all the other controllers.
Installation Installation The controller consists of the housing with the electronics and the back panel with the terminals. It is suitable for panel, wall, and top hat rail mounting (Fig. 9). Panel mounting 1. Remove both screws (1). 2. Pull apart the controller housing and back panel. 3.
Page 89
Installation Panel mounting Back of the controller Controller housing Wall mounting Top hat rail mounting Fig. 9 · Installation EB 5179 EN...
Electrical connection Caution! For electrical installation, you are required to observe the relevant electrotechnical regulations of the country of use as well as the regulations of the local power suppliers. Make sure all electri- cal work is performed by trained and experienced personnel! Notes on installing the electrical connections Install the 230 V power supply lines and the signal lines separately! To increase noise immu- nity, observe a minimum distance of 10 cm between the lines.
Page 91
Connecting the sensors Cables with a minimum cross-section of 2 x 0.5 mm² can be connected to the terminals at the back panel of the housing. Connecting the actuators Connect cables with at least 1.5 mm² suitable for damp locations to the terminals of the control- ler output.
Page 92
System Anl 1 3 1 2 Option: Type 5244, Type 5257-5 System Anl 2 Option: 3 1 2 Option: Type 5244, Type 5257-5 Option: Type 5244, Type 5257-5 Type 5244, Type 5257-5 EB 5179 EN...
Page 93
System Anl 3 Option: Type 5244, Type 5257-5 System Anl 4 Option: Type 5244, Type 5257-5 EB 5179 EN...
Page 94
System Anl 5 Option: Type 5244, Type 5257-5 System Anl 6 Option: Type 5244, Type 5257-5 EB 5179 EN...
Page 95
System Anl 7 Option: Type 5244, Type 5257-5 System Anl 8 3 1 2 Option: Type 5244, Type 5257-5 EB 5179 EN...
Page 96
Electrical connection System Anl 9 Option: Type 5244, Type 5257-5 System Anl 10 3 1 2 Voltage supply 24 V/30 mA Relay: Phoenix Contact, Type PLC-BSC-24 DC/21, Article no. 29 66 016 EB 5179 EN...
Appendix Appendix 12.1 Function block lists Co1 to Co3: Heating circuit 1 to 3 Comments Function block parameters / Range of values (default settings) Fb Function 00 Room sensor Co1, 2, 3 -> Fb00 = ON: Room sensor active RF1, 2, 3 In systems Anl 3, 5 and 8 only for optimization and display 01 Return flow sensor Co1, 2, 3 ->...
Page 98
Appendix Comments Fb Function Function block parameters / Range of values (default settings) 09 RK switched off Co1, 2, 3 -> Fb09 = ON: UP still runs until 1 x T when switch at The flow sensor is no longer be read. MAN-CLOSED 10 4-point character- Co1, 2, 3 ->...
Page 99
Appendix Comments Fb Function Function block parameters / Range of values (default settings) 17 Flow sensor OFF 6, 9 Co1, 2, 3 -> Fb17 = ON: Deactivate flow sensor with room tempera- ture-dependent control 18 Differential temper- Co1, 2, 3 -> Fb18 = ON: Only for mixer circuits ature control using Function block parameters: variable weighting...
Page 100
Appendix Comments Fb Function Function block parameters / Range of values (default setting) 06 Reverse control Co4 -> Fb06 = ON: Reverse control 1, 3, 6 Co4 -> Fb06 = OFF: Set-back operation Function block parameters: Activate priority in case of deviation / 0 to 30 °C (0 °C) 07 Time until reverse Co4 ->...
Page 101
Appendix Co5: General functions and pre-control circuit Comments Function block parameters / Range of values (default setting) Fb Function 00 Flow sensor Co5 -> Fb00 = ON: secondary VFsek In systems Anl 6 and 9 not possible with Co5 -> Fb06 = ON 01 Return flow sensor Co5 ->...
Page 102
Appendix Comments Fb Function Function block parameters / Range of values (default setting) 09 Pulse input for flow Co5 -> Fb09 = ON: Type of limitation rate or capacity 6, 9 Option: U: Flow rate limitation P: Capacity limitation limitation CONST Limitation constant 4-Pt:...
Page 103
Comments Fb Function Function block parameters / Range of values (default setting)
Page 104
Appendix Co6: Sensor initialization Comments Fb Function Function block parameters / Range of values (default setting) 00 Sensor selection Co6 -> Fb00 = ON: Pt 100; Pt 1000 general Co6 -> Fb00 = OFF: Pt 100; PTC Sensor input 1 Any sensor inputs that are different from the settings for function block Fb00 sensor input 17...
Page 105
Appendix Co8: Error initialization Comments Function block parameters / Range of values (default setting) Fb Function 00 Dial-up also upon CO8 -> Fb00 = ON: Dial-up to the building control station corrected fault both when a fault was detected and a fault was corrected CO8 ->...
Page 106
Appendix Comments FB Function Function block parameters / Range of values (default setting) Meter bus #1 OFF CO9 -> Fb21, 22, 23 = ON: Function block parameters: Meter bus address WMZ_ / 0 to 255 (255) Meter bus #3 Model code WMZ_ / P15, PS2, 1434, CAL3, APAtO, SLS (1434) Reading mode WMZ_ / 24h, con, CoiL (con) Fb Function block, WE Default setting EB 5179 EN...
Appendix 12.3 Display The following displays are typical displays that can appear. Icons at the edge of the display may vary depending on the operating mode and how the con- troller is configured; they cannot be shown in this case. Inf1 to Inf3: Heating circuits HK1 to HK3 Display Parameter designation...
Page 122
Appendix Display Parameter designation 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Tendency of the room temperature Valve position The actual value of the analog output with differential temperature control using variable weighting factors Press enter key to confirm.
Page 123
Appendix Display Parameter designation 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 Vacations Press enter key to confirm.. The first vacation period is displayed. Press arrow key to scroll between other vacation periods.
Page 124
Appendix Display Parameter designation Storage tank temperature at sensor SF2 Press enter key to confirm. The set point is displayed. Storage tank temperature at return flow sensor Press enter key to confirm. The set point is displayed. Control signal for continuous-action control Only with Co4 ->...
Page 125
Appendix Inf5: District heating circuit Display Parameter designation Charging temperature Press enter key to confirm. The set point is displayed. Return flow temperature at sensor RüF or RüFprim Press enter key to confirm. The set point is displayed. Valve position Only with Co5 ->...
Page 126
Appendix InF7: LON communication Display Parameter designation Connected LON controller, e.g. a TROVIS 5174 with LON address 2 Press enter key. “FSr“ of the corresponding controller is displayed. Inf8: Error status register/sensor failure Display Parameter designation Error status register FSr 1 0 1 2 3 4 5 6 7 8 910 13141516171819202122 2324 Press enter key.
Page 127
Appendix InF9: Communication (only with Co9 -> Fb01 = ON, Co9 -> Fb06 = ON or Co9 -> Fb10 = ON) In the main display loop, the connection status appears in the InF9 level and only exists when the modem, SMS or fax function is active, otherwise just “END“ appears on the display. In this display, the applicable status from the following list of states appears when a modem connection is established.
Appendix 12.4 Sensor resistance tables Resistance values with PTC resistors Type 5224 Outdoor Temperature Sensors, Type 5264 and Type 5265 Flow and Return Flow Temperature Sensors, Type 5264 Storage Tank Temperature Sensors –20 –10 °C Ω 694 757 825 896 971 1010 1050 1132 1219 1309 1402 1500 1601 1706 1815 1925 °C 10 Type 5244 Sensor Ω...
Appendix 12.5 Technical data Inputs Sensor inputs Max. 17 configurable inputs for temperature sensors Pt 100, Pt 1000, Ni 200, Ni 1000 und PTC, NTC, 0–10 V, 0/4–20 mA or binary alarms (heating/DHW circuit) 5 flow temperature sensors, 2 outdoor temperature sensors, 2 return flow temperature sensors, 2 room temperature sensors, 2 storage tank temperature sensors...
Appendix 12.6 Customer data Station Operator Relevant SAMSON office System code number Function block settings in configuration levels Fb00 Fb01 Fb02 Fb03 Fb04 Fb05 Fb06 Fb07 Fb08 Fb09 Fb10 Fb11 Fb12 Fb13 Fb14 Fb15 Fb16 Fb17 Fb18 Fb19 Fb20 Fb21...
Page 131
Appendix PA1 to PA3: Heating circuits HK1 to HK3 Parameters Range of values Gradient, flow 0.4 to 3.2 Level, flow –30 to 30 °C Maximum flow temperature 20 to 130 °C Minimum flow temperature 20 to 130 °C Set-back difference 0 to 50 °C Gradient, return flow 0.4 to 3.2...
Page 132
Appendix Parameters Range of values Times-of-use Monday Start – Stop (1) 00:00 to 24:00 h Monday Start – Stop (2) 00:00 to 24:00 h Tuesday Start – Stop (1) 00:00 to 24:00 h Tuesday Start – Stop (2) 00:00 to 24:00 h Wednesday Start –...
Page 133
Appendix Differential temperature control using 0 to 40 °C variable weighting factors (Fb18 = ON) Function block parameters Co1, Co2, Co3 Analog value max. (Fb18 = ON) 0 to 100 % Analog value min. (Fb18 = ON) 0 to 100 % Vacations (Start –...
Page 134
Appendix PA4: DHW heating Parameters Range of values DHW demand ON 20 to 90 °C DHW demand OFF 20 to 90 °C Hysteresis 0 to 30 °C Charging temperature 20 to 90 °C Heat exchanger charging pump, 20 to 90 °C deactivation value Storage tank charging pump, 20 to 90 °C...
Page 135
Appendix Function block parameters Co4 Limitation factor (Fb02 = ON) 0 to 25.5 Activate priority in case of deviation 0 to 30 °C (Fb06 = ON) Day of week (Fb08 = ON) 0, 1 to 7 Disinfection temperature (Fb08 = ON) 60 to 90 °C Boost of charging temperature 0 to 30 °C...
Page 136
Appendix Parameters Range of values Outdoor temperature, point 3 –30 to 90 °C Outdoor temperature, point 4 –30 to 90 °C Return flow temperature, point 1 20 to 90 °C Return flow temperature, point 2 20 to 90 °C Return flow temperature, point 3 20 to 90 °C Return flow temperature, point 4 20 to 90 °C...
Page 137
Appendix Co9: Modbus and meter bus communication Parameters Range of values Station number (ST.-NR) 1 to 247, 999 Baud rate (BAUD) 300 to 19200 Cyclic initialization (I) 1 to 255 min Modem dial interval between calls (P) 0 to 255 min Modem timeout (t) 0 to 255 min Number of redial attempts (C)
Page 138
Index Index 4-point characteristic ....40 Display ......9 Adaptation .
Page 139
Index Interface Position feedback ....51 Meter bus..... 81 Priority RS-232-C.
Page 140
Index Time delays, compensating for ..61 Time-controlled operation ... . . 8 Universal inputs ....24 Times-of-use copying .
Page 141
00:00 InF1 InF1: Heating circuit 1 InF2 InF2: Heating circuit 2 InF3: Heating circuit 3 Error InF3 InF4: DHW heating InF5: Primary control circuit Operating level InF4 (see section 1 for operation) InF7: LON communication InF8: Error status register bIn-E InF5 InF9: Communication...
Page 142
SAMSON AG · MESS- UND REGELTECHNIK Weismüllerstraße 3 · 60314 Frankfurt am Main · Germany Phone: +49 69 4009-0 · Fax: +49 69 4009-1507 EB 5179 EN Internet: http://www.samson.de...