District heating controller
Table of Contents

Advertisement

Display
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
STOP
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
STOP
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Parameter designation
Range of values (default settings)
DHW demand OFF
˚C
20 to 90 °C (45 °C)
Charging temperature
˚C
20 to 90 °C (55 °C)
Heat exchanger charging pump, deactivation limit
˚C
20 to 90 °C (50 °C)
Lag of heat exchanger charging pump until the heat exchanger
flow temperature falls below the limit.
Storage tank charging pump, deactivation limit
20 to 90 °C (50 °C)
Lag of storage tank charging pump until the heat exchanger flow
temperature falls below the limit.
Return flow limitation temperature for DHW
˚C
20 to 90 °C (45 °C)
Appendix
113